Page 32
10.8 Electrode replacement
» Remove and open cylinder, as described in
section "Removal and reinstallation of the
steam cylinder".
When mounting the electrodes, make sure
that the hand nut colours corresponding with
the wiring colours remain in the same posi-
tion as before in order to omit any unwanted
shift of electrical potential. Hence, the hand
nut positions must be recorded before they
are removed. During reassembly, particular
care must be taken to ensure that no grey
wire is connected to the electrode plug next
to the (grey) sensor electrode hand nut.
» Unscrew hand nuts
»
Remove electrodes (48)
»
Install new electrodes (48). Make
sure that the electrodes are posi-
tioned correctly (see exploded view).
»
Hand tighten the nuts (49).
»
Use solvent-free, HygroMatik-quality
o-rings (for flange, electrodes, cylin-
der base and steam hose adapter).
»
Assemble steam cylinder
»
Plug the electrode plugs (4) directly
onto the electrodes (48)
»
Install the steam cylinder
Genuine electrode length
Hygromatik large area electrodes made from
stainless steel have the following genuine
lengths:
Electrode wear
Eelctrode wear depends on:
•
composition and conductivity of the
supply water
•
the amount of steam produced
In case of the electrodes being burned-off to
less than one third to half of their genuine
length, electrode replacement should be
made.
When cylinder water maximum level is
detected for a period of 60 mins, an error
message (s. unit control chapter, error mes-
sage section in the co-applicable „Controls
Standard“ manual) is generated and unit
operation is cut. At the latest, electrode
replacement should then be made.
3OHDVHQRWH
49
48
Device
model
MS05 MS10
Length
[mm]
155
155
3OHDVHQRWH