background image

2.0 Product Information                                                                                      

 

_________________________________________________________________________________________ 
8                                                                                                                                                          CC1132751C 

2.5 Technical Data HR04-HR07 

 

Model Number

 

HR04

 

HR05

 

HR07

 

HR07RS

 

PERFORMANCE DATA (50Hz)

 

F.A.D. litres/sec (cfm) @ 7 bar/102 psi 

11.42 (24.20) 

15.35 (32.52) 

21.23 (45.00) 

20.53 (42.50) 

F.A.D. litres/sec (cfm) @ 10 bar/145 psi 

9.50 (20.10) 

12.75 (27.02) 

17.34 (36.75) 

17.37 (36.80) 

PERFORMANCE DATA (60Hz)

 

F.A.D. litres/sec (cfm) @ 7 bar/102 psi 

10.05 (21.30) 

15.06 (31.90) 

18.17 (38.50) 

20.53 (42.50) 

F.A.D. litres/sec (cfm) @ 10 bar/145 psi 

8.35 (17.70) 

10.34 (21.90) 

14.21 (30.10) 

17.37 (36.80) 

PERFORMANCE

 

Power - kW (hp) 

4.0 (5.5) 

5.5 (7.5) 

7.5 (10) 

Noise Level - dBA 

67 

69 

Starter Type 

DOL (60Hz) and SD (50Hz) 

Inverter 

Drive Type 

Direct 

Operating Controls 

Continuous Run, Automatic Stop/Start,  

Reduced Energy Vent System 

Variable 

Rotation Speed - rev/min 50Hz (60Hz) 

1450 (1760) 

1100 *-2150 * 

Ambient Temperature Range °C (°F) 

0 to 45 (32 to 113) 

0 to 40  

(32 to 104) 

Maximum Relative Humidity % 

85 non-condensing 

Air Discharge Temp - °C (°F) above ambient 

<6 (43) 

<8 (46) 

<10 (50) 

FACTORY SETTINGS

 

Nominal Pressure – bar (psi) 

7.0 or 10.0 (102 or 145) 

7.0 (102) 

Minimum Pressure Valve – bar (psi) 

5.5 to 6.0 (80 to 87) 

Load/Cut-in Pressure – bar (psi) 

6.5 or 9.5 (94 or 138) 

7.0 (102) 

Unload/Cut-out Pressure – bar (psi) 

7.5 or 10.5 (109 or 152) 

7.5 (109) 

Servo Valve – bar (psi) 

8.0 or 11.0 (116 or 160) 

8.0 (116) 

Vent Down Run Time @ 7 bar – sec 

60 

Vent Down Run Time @ 10 bar – sec 

90 

Pressure Display Units 

0 (bar) (1 = psi, 2 = kpa) 

Temperature Display Units 

0 = °C (1 = °F) 

Vacuum Relief Valve 

1.5 turns anti-clockwise 

INSTALLATION 

 

Dimensions D x W x H –mm  

685 x 630 x 1078  

Weights - kg 

220 

230 

Air Outlet Size - Rp 

3/4 

Minimum Room Volume - m

3

 

15 

Air Inlet/Outlet Area - m

2

 

0.3 

Ventilation Rate - m

3

/h 

2000 

Cooling Air Flow m

3

/h (cfm) 

1850 (1089) 

Recommended Air Receiver Capacity - litres 

250 

COMPRESSOR OIL

 

Approved compressor oil 

Fluid Force Red 2000 (Mineral) and HPO (Synthetic) 

Oil Capacity – litres 

ELECTRICAL

 

Starter reference 200/575V 3PH 60Hz DOL 

CC1118983 

 

Circuit diagram 200/575V 3PH 60Hz DOL 

CZ77996 

 

Starter reference 400V 3PH 50Hz SD 

CC1054889 

 

Circuit diagram 400V 3PH 50Hz SD 

CZ77989 

 

Starter reference 400/460 3PH 50/60Hz RS 

 

CC1054890 

Circuit diagram 400/460V 3PH 50/60Hz RS 

 

CZ77990 

*Alternative speed settings may be required depending on application and duty cycle 

Содержание HR04

Страница 1: ...HR04 HR07 Models User Handbook Original Instructions CC1132751D 10 2018 GB...

Страница 2: ......

Страница 3: ...3 Compressor Assembly Fig 4 2 12 4 4 Electronic Controller 12 5 0 Operating Instructions 13 5 1 Checking Procedure Before Starting 13 5 2 Operator Control Keys Fig 5 1 13 5 3 Status Display Lights 13...

Страница 4: ...17 7 8 Oil Separator Fig 7 1 17 7 9 Oil Cooler Aftercooler Fig 7 2 18 7 10 Cabinet Air Filter Fig 7 2 18 7 11 Electric Motor 18 7 12 Electrical Connections 18 7 13 Service Schedule 18 8 0 Controller...

Страница 5: ...odel HR04ER07 4035S000 50Hz model HR04ED07 4035S000 50Hz model HR04ERD07 4035S000 50Hz model HR04E07 5736D005 60Hz model HR04E10 2036D005 60Hz model HR04E10 4035S000 50Hz model HR04ER10 4035S000 50Hz...

Страница 6: ...Warning unit is remotely controlled and may start without warning Read the instruction manual Do not operate the machine the machine without the guard being fitted Warning do not start the machine wi...

Страница 7: ...ed over a period of time may cause problems that affect the performance and reliability of this compressor Problems may occur when compressors run for short periods on low air demand where they don t...

Страница 8: ...ETTINGS Nominal Pressure bar psi 7 0 or 10 0 102 or 145 7 0 102 Minimum Pressure Valve bar psi 5 5 to 6 0 80 to 87 Load Cut in Pressure bar psi 6 5 or 9 5 94 or 138 7 0 102 Unload Cut out Pressure bar...

Страница 9: ...low of the compressor Total resistance of the system must not exceed 50 mbar If resistance is expected to be greater fan assistance will be required 3 4 Electrical Connections WARNING CONNECTION TO OR...

Страница 10: ...otation is correct by observing pressure rise on the compressor gauge Cooling fan operation is clockwise all RS units have automatic stop start cooling fans that cut in at 85 C 185 F operating tempera...

Страница 11: ...ir demands The compressor will load unload and stop start automatically in response to air demand Motor restarts are set to 10 times per hour for single speed units and 30 times for RS units Run on ti...

Страница 12: ...d adjacent to the oil filter The compressor is filled and topped up with oil via the oil filler P The sight glass O will be full when oil overflows from the level plug orifice Q Oil is drained from th...

Страница 13: ...ssure are viewed here The third row shows status fault and warning messages The HYDROVANE Pro is fitted with two light signals green red Flashing system is ready the motor may start up automatically a...

Страница 14: ...sure set point the REVS Reduced Energy Venting System sequence will begin If there is an air demand during the REVS run on time sequence the compressor returns to full load operation If there is no ai...

Страница 15: ...IN POINT or p2 TARGET PRESSURE RS e RUN ON TIME f AUTOMATIC OPERATION g ENABLE REMOTE START h TIMER CONTROL i p2 TIMER CONTROL j AUTO RESTART k POWER LOSS TIME l START UP DELAY m DRYER PRE RUN n RS48...

Страница 16: ...this is the basis for accurate timer operations Go to the TIMER CONTROL sub menu use the or key to select from seven different timer units The status line of each switching unit is as follows a b c d...

Страница 17: ...SAFETY NOTICE ADVISING THAT WORK IS BEING CARRIED OUT ON THE COMPRESSOR CLOSE THE AIR OUTLET VALVE TO ISOLATE THE COMPRESSOR FROM THE AIRLINE SYSTEM FIT A SAFETY NOTICE ADVISING THAT IT IS NOT TO BE...

Страница 18: ...special attention to power connections cables connected to contactors and incoming terminals and ensure all earthing wiring is present and undamaged Close the starter panel door and lock with the key...

Страница 19: ...d X X X X Check motor conduit cables secure X X X X Check motor for damage X Check motor starter for loose connections X X X X Check motor for vibration X X X X Check flexible control pipes X X X Chec...

Страница 20: ...motor for damage X Check motor starter for loose connections X X X Check motor for vibration X X X Check flexible control pipes X X Check oil seal for leakage X X Check drive media key X Check starte...

Страница 21: ...t now starts automatically after a previously set time f WARNING START IN Alternating with AFTER DRYER PRE RUN The unit has been switched on and is ready The unit starts automatically after the dryer...

Страница 22: ...he Engineering Department Gardner Denver Ltd Web www hydrovaneproducts com www gardnerdenver com E mail sales compair com hydrovane nfo uk gardnerdenver com CC1132751D hydrovane USA 1301 North Euclid...

Страница 23: ......

Страница 24: ...ons for hydrovane Various Applications Global Expertise Gardner Denver Ltd Claybrook Drive Redditc h Worc estershire B98 ODS UK T 44 0 1527 525522 838200 E hydrovane info uk gardnerdenver com www hydr...

Отзывы: