CLEANING THE BOILER
Before applying mentioned services to the boiler;electric must be cut off from the main switch,fuel valves
must be closed, control panel and the burner must be protected for avoiding any possible damage.
Smoke Channels Cleaning
Because of the soot layer on heating surfaces, 100 °C increase on flue temperature brings out a % 5
decrease on efficiency.
By pulling out the M16 screws and stamps on the 4 hinges which connects door to the front section,
open the burner door. Clean the burning room, take turbulators out and clean horizontal smoke channels
(2nd and 3rd pass). Than clean the turbulator and put them in to the channels. Close the burner door
strictly.In this cleaning operation soot layer may occur in flue area.This soot particules can be cleaned
by seperating horizontal smoke channels from boiler flue. After this operation these two must be connec-
ted again and must be tested for leakage.
The time period for cleaning service is variable according to the fuel type of the boiler and period of use.
In boiler cleaning operation ceramic ropes that isolate front door with front section and flue with back
section must be controlled and must be renewed if needed.
BURNER DOOR AND BURNER CONNECTION
Burner Door
In burner connection process there must not be any
empty space left between the front door and the
burner barell.All connection points must be covered
with isolation material for avoiding any air leakage
possibility.
A metal sheet is used for easier assembling of the
burner to the door. This metal sheet is made of 12
mm thickness and in the dimensions of 240x240 mm
(1).
The isolation of the burner door is made of a special
thermal ceramic which is durable up to 1250ºC and
has no defections on human health (2). Please be
sure that this isolation plate is carried carefully and
intensivly during transportation.
There is a ceramic rope fit in to the channels of iso-
lation door.This prevents leakages between isolation
door and front section of the boiler. After repairing
or cleaning service the doors connection with the
front section must be done properly,strictly.
OM series boilers doors are available for opening to
both sides. This brings advantages of assembling,
reparing and other operations.
A tempered ceramic glass is placed on to the burner
door for watching flame inside (3).
35
36
2
1
3
1
45º
Содержание 0M 08
Страница 1: ...Oil Gas Fired Boiler Cast iron Triple Pass Design 378 kW to 930 kW...
Страница 5: ...OM SERIES CAST IRON BOILER TECNICAL DATA I...
Страница 6: ...OM SERIES CAST IRON BOILER TECNICAL DATA II...
Страница 10: ...DIAGRAM OF A SAMPLE SINGLE BOILER HEATING CIRCUIT WITH WATER HEATER 16 OM SERIES CAST IRON BOILER...
Страница 13: ...BOILER CONTROL PANELS Standard Boiler Control Panel Single Level Standard Boiler Control Panel Dual Level 20...