WATER CIRCULATION PRINCIPAL
For healthy working conditions of the boiler,temperature difference between water forward and water
return must not be more than 20 °C
And boiler must not be started or work under the water volumes which is mentioned in the above table.
Boiler
Capacity
Type
kCal/h
kW
Water
Water Part
Water
Water Part
Volume
Resistance
Volume
resistance
m³/h
mbar
m³/h
mbar
OM 06
325.000
377,9
21,67
102
16,25
54
OM 07
385.000
447,7
25,67
147
19,25
80
OM 08
435.000
505,8
29,00
180
21,75
105
OM 09
485.000
564,0
32,33
160
24,25
78
OM 10
525.000
610,5
35,00
175
26,25
88
OM 11
570.000
662,8
38,00
200
28,50
115
OM 12
615.000
715,1
41,00
220
30,75
130
OM 13
665.000
773,3
44,33
160
33,25
85
OM 14
715.000
831,4
47,67
180
35,75
90
OM 15
755.000
877,9
50,33
205
37,75
125
OM 16
800.000
930,2
53,33
220
40,00
140
¨
t = 15 K
¨
t = 20 K
17
10
100
500
400
200
100
50
30
10
20
15
25
30
20
15
40 50
150
Содержание 0M 08
Страница 1: ...Oil Gas Fired Boiler Cast iron Triple Pass Design 378 kW to 930 kW...
Страница 5: ...OM SERIES CAST IRON BOILER TECNICAL DATA I...
Страница 6: ...OM SERIES CAST IRON BOILER TECNICAL DATA II...
Страница 10: ...DIAGRAM OF A SAMPLE SINGLE BOILER HEATING CIRCUIT WITH WATER HEATER 16 OM SERIES CAST IRON BOILER...
Страница 13: ...BOILER CONTROL PANELS Standard Boiler Control Panel Single Level Standard Boiler Control Panel Dual Level 20...