BOILER ROOM AIRING
There are three reasons for fresh air in boiler rooms.
1.The burning air needed for the burning in the boiler
2.The air needed for prevention of dirt and dust,for releasing the gases and fuel to put out
3.The air needed for overheating in the boiler room.
Airing for first two reasons are continously needed.The thirs one is needed
especially for the boilers which are working on summer time.
Maximum temperature for the boiler room must be 32 °C
Boiler room must be protected against freezing.
If the fuel is
natural gas
Boiler
Type
* If natural airing system is used. ** Ventilating aring
system is used
***
Bottom
Up
Bottom
Up
***Bottom value shows the clean air input up shows the
OM 06
1.971
985
1.224
816
air output.
OM 07
2.285
1.142
1.450
967
OM 08
2.546
1.273
1.639
1.093
OM 09
2.808
1.404
1.827
1.218
OM 10
3.017
1.509
1.978
1.319
OM 11
3.253
1.626
2.147
1.432
OM 12
3.488
1.744
2.317
1.545
OM 13
3.750
1.875
2.505
1.670
OM 14
4.011
2.006
2.694
1.796
OM 15
4.221
2.110
2.844
1.896
OM 16
4.456
2.228
3.014
2.009
CHECKINGS AND STARTING THE BOILER
Pre Controls
Following controls must be done before starting the boiler. If there are any problems or failure, boiler
must not be started.
Water level of the boiler must be controlled. Water must be added to the boiler if the water level is low.
Please call technicians if there is a water leakage. Leakage must be prevented before starting the
boiler. If there is a leakage in the plumbing system,boiler must be started after repair.
Flue connections must be controlled. Boiler must not be started before repairing the connection if there
is a problem.
Area must be properly air conditioned.
Gas valves must be checked as if they are on if gas fuel is used in the boiler.
Liquid fuel level of the tank must be controlled and fuel valve must be opened if liquid fuel is used in
the boiler. Fuel - burner connection must be controlled.If there are any problems filters must be cleaned.
Working and the directions of the pumps must be controlled.
Electric ssytem of the control panel must be controlled.
All water and gas valves of the boiler must be opened.
All other connections must be controlld according to the system options.
Starting The Boiler
Turn the main electric switch of the boiler room on. Working lamp will be on.
Start the circulation pump
Turn the ''on / off '' switch of the burner to the mode ''on'' (Check the burner instructions manual.)
The indicator light will be on .
**Volume of Air
*Net Cross Section of
Needed for Force Airing
( m³/h )
Open for Natural Airing
( cm² )
Содержание 0M 08
Страница 1: ...Oil Gas Fired Boiler Cast iron Triple Pass Design 378 kW to 930 kW...
Страница 5: ...OM SERIES CAST IRON BOILER TECNICAL DATA I...
Страница 6: ...OM SERIES CAST IRON BOILER TECNICAL DATA II...
Страница 10: ...DIAGRAM OF A SAMPLE SINGLE BOILER HEATING CIRCUIT WITH WATER HEATER 16 OM SERIES CAST IRON BOILER...
Страница 13: ...BOILER CONTROL PANELS Standard Boiler Control Panel Single Level Standard Boiler Control Panel Dual Level 20...