Pump 
Notes

9

2.  Check  valve  may  be  partially

clogged.    Raise  lever  up  and
down to clear.

3.  Pump  may  be  running  in  the

wrong  direction.  Low  speed
pumps  can  operate  in  reverse
direction  without  much  noise
or vibration.

4.  Discharge  head  may  be  too

high.  Check  total  head  with
gauge  when  the  pump  is
operating.

5.  If pump has been in service for

some  time  and  capacity  falls
off, remove pump and inspect
impeller for wear.

Motor  stops  and  then  restarts
after  short  period  but  overload
heaters in starter do not trip.

1.  This  indicates  heat  sensors  in

the  motor  are  tripping  due  to
excessive  heat.    Impeller  may
be  partially  clogged  giving
sustained  overload  but  not
high  enough  to  trip  overload
heaters.

2.  Pump  may  be  operating  on  a

short cycle due to faulty check
valve in the wet well.

Содержание DRY PIT

Страница 1: ...NOTE To the installer Please make sure you provide this manual to the owner of the equipment or to the responsible party who maintains the system Installation and Service Manual Wastewater Lift Statio...

Страница 2: ...rature The sensors are connected in series with the motor starter coil so that the starter is tripped if heat sensor opens The motor starter is equipped with overload heaters so all normal overloads a...

Страница 3: ...ng Pump Stand The pump will ship from the factory on a dry pit pump stand The suction and discharge of the pump will be oriented at the factory per the prescribed customer order The dry pit pump must...

Страница 4: ...p to assist in troubleshooting potential performance problems NEMA 4 Junction Box Optional A NEMA 4 junction box should be used to make power and control connections if electrical control panel is to...

Страница 5: ...ace Control level can be changed at any time by loosening the snubber and readjusting cord length In either a simplex or duplex system the lower or turn off control is set just above the drywell inlet...

Страница 6: ...the override control level 7 Turn both switches to Auto position and both pumps should start and operate together until level drops to turn off point 8 Repeat this operation cycle several times befor...

Страница 7: ...lted in clamp ring 7 After ring is removed turn housing upright and bump on hardwood blocks This should jar the stator loose and allow it to drop out 8 Thoroughly clean housing before replacing new st...

Страница 8: ...n inner face of the bearing when replacing Pressing on the outer face can damage the bearing Bearings are standard size that can be obtained from any bearing supply house or can be obtained from the f...

Страница 9: ...mp is operating 5 If pump has been in service for some time and capacity falls off remove pump and inspect impeller for wear Motor stops and then restarts after short period but overload heaters in st...

Страница 10: ...dance with the printed instructions provided b to failures resulting from abuse accident or negligence c to normal maintenance services and parts used in connection with such service d to units which...

Страница 11: ......

Страница 12: ...Line Voltage _________________________________Actual ___________________________________ Voltage to Pumps _____________________________________Actual ___________________________________ Type of Junct...

Отзывы: