Secondary Address
– Secondary address on the M-Bus. This address is used to
identify a meter if there are more meters with the same primary address (
Address
field) on the bus. Secondary Address is non-editable and consists of a
manufacturer-defined part and the Address field (last 2 characters).
Medium
– Type of the meter (electricity, gas …). The medium is not editable.
Enable
– Enables or disables the meter within HWg-PWR. When a meter is
disabled, values are not detected or read but the configured parameters remain
stored. This can be used to temporarily turn off the reading and recording for a
meter (during maintenance etc.)
Address
– Primary address on the M-Bus. The address is entered as one byte
(0-255).
Serial Baudrate
– M-Bus communication speed for the particular meter. By
default, 2400 Baud is configured. Meters with different communication speeds
can coexist on a single bus; this parameter sets the speed for a particular meter.
Serial Parity
– M-Bus communication parity. As with the baudrate, parity can be
specified individually for each meter.
Name
– Meter name. Identifies the meter within HWg-PWR – in graphs, XML and
SNMP.
Scan Value
– Reads out the values and their parameters from the meter. See
First
Steps
.
Parameter Table section
The
Parameter Table
section displays information about discovered values from a
particular meter – their names (
Name
), units of measurement (
Unit
) and current readings
(
Value
). Each value is assigned a unique ID within HWG-PWR for use in XML and SNMP
communication. To edit a value, its parameters and properties, click “
Edit
” on the
corresponding line.
Содержание HWg-PWR
Страница 1: ...HWg PWR MANUAL...
Страница 7: ...HWg PWR M Bus IP energy meter SNMP WEB HW group www HW group com page 7 Connecting meters to HWg PWR...
Страница 28: ...HWg PWR M Bus IP energy meter SNMP WEB HW group www HW group com page 28 Mechanical...
Страница 29: ...HWg PWR M Bus IP energy meter SNMP WEB HW group www HW group com page 29...
Страница 30: ...HWg PWR M Bus IP energy meter SNMP WEB HW group www HW group com page 30...
Страница 31: ...HWg PWR M Bus IP energy meter SNMP WEB HW group www HW group com page 31...