background image

IMPACT Rear Roll-in

HUSSMANN CORPORATION • BRIDGETON, MO 63044-2483  U.S.A.

P/N 0435045A

3-1

WASTE OUTLET

A waste outlet is located at the back of the upper
fan plenum, 1 

1

/

4

in. (32 mm) from either end of

the case. 

It is the responsibility of the installing contractor
to supply and connect drip pipe external to the
case. External drip pipe may be flexible or rigid.

INSTALLING DRIP PIPING

Poorly or improperly installed drip pipes can 
seriously interfere with the case’s operation and
result in costly maintenance and product losses.
Please follow the recommendations listed below
when installing drip pipes to ensure proper instal-
lation.

1. Never use drip piping smaller than the nomi-

nal diameter of the pipe in the case.

2. When connecting drip piping, the “water

seal” must be used as part of the drip piping
to prevent air leakage or insect entrance.
Never use two water seals in series in any one
drip pipe.

D

OUBLE WATER SEALS IN SERIES

WILL CAUSE AN AIR LOCK AND PREVENT

DRAINING

.

3. Pitch the drip piping in the direction of flow.

There should be a minimum pitch of 

1

/

8

in.

per ft (3 mm per 300 mm).

4. Avoid long runs of drip piping. Long runs

make it impossible to provide the pitch 
necessary for good drainage.

5. Provide a suitable air break between

flood rim of the floor drain and outlet
of drip pipe. To meet code on low base
cases, it may be necessary to install a
field-supplied drip pipe reducer. An
alternative is to cut the last section of
drip pipe at an angle.

6. Prevent drip pipes from freezing:

A.  Do NOT install drip pipes in contact with
uninsulated suction lines. Suction lines should
be insulated with a nonabsorbent insulation
material. 

B.  Where drip pipes are located in dead air
spaces, such as between cases or between a
case and a store wall, provide means to 
prevent freezing.

SEALING SPLASHGUARD TO FLOOR

Stainless steel splashguards may be sealed to the
floor using a vinyl cove base trim. The size of
trim needed will depend on how much the floor is
out of level.

To install the trim to the splashguard:

1. Remove all dirt, wax and grease from the area

of the splashguard where adhesion will be
necessary. This is to ensure a good and secure
installation.

2. Apply a good contact cement to the cove trim

and allow proper drying time according to the
directions supplied with the cement.

DRIP PIPING AND SPLASHGUARDS

Waste Outlet at End
(connect drip pipe here)

Содержание IMPACT D5RRI

Страница 1: ...ing or Suspended Merchandisers Installed in Walk in Cooler Exterior Walls Installation Operation Service Manual Shipped With Case Technical Data Sheets P N 0435045A Impact Series June 2006 IMPORTANT K...

Страница 2: ...Installing Drip Piping 3 1 Sealing Splashguard to Floor 3 1 START UP OPERATION Start up 4 1 Stocking 4 1 Optional Shelving 4 1 Accessories 4 2 Load Limits 4 2 Installing FDA NSF Required Thermometer 4...

Страница 3: ...ith the D5L LOCATION These cases are designed for displaying products in air conditioned stores where temperature is maintained at or below the ANSI NSF 7 specified level and relative humidity is main...

Страница 4: ...orted while it is being unfastened from the skid and when it is removed from the skid Once the skid has been unfastened never leave the fixture unsupported or unattended until it has been anchored LEV...

Страница 5: ...installation Two 15 8 x 15 8 inch 41 x 41 mm channel struts are provided for hanging the coil package These struts extend the full length of the case and are bolted to the case at the factory Use 1 2...

Страница 6: ...ing to NSF guidelines The channel struts with clamping nuts are provid ed to fasten the suspending rods When tightening 1 2 in 12 7 mm threaded rods into nuts ensure that the rods are firmly screwed i...

Страница 7: ...he track 3 Hang curtains on hangers JOINING Sectional construction means that two or more merchandisers may be joined in line yielding one long continuous display requiring only one pair of ends Joint...

Страница 8: ...o prevent drip page from condensate Line Sizing Refrigerant lines should be sized as shown on the refrigeration legend that is furnished for the store or according to ASHRAE guidelines Refer to the in...

Страница 9: ...ad and again after the second third Do not reduce below the case suction line size Case suction lines should enter at the top of the branch line LIQUID LINE May be reduced by one size after one half t...

Страница 10: ...terminated defrost only Refer to the case data sheet shipped with this manual for correct settings DEFROST SEQUENCES These merchandisers require defrost cycles for proper operation Refer to the data s...

Страница 11: ...TE FOR COMPONENT AMPERES IDENTIFICATION OF WIRING Leads for all electrical circuits are identified by colored plastic bands These bands correspond to the color code sticker shown below located inside...

Страница 12: ...er 300 mm 4 Avoid long runs of drip piping Long runs make it impossible to provide the pitch necessary for good drainage 5 Provide a suitable air break between flood rim of the floor drain and outlet...

Страница 13: ...nstall the trim to the splashguard so that it is lying flush with the floor The Cove Trim may be sealed to the floor using a silicone sealer P N 0435045A WWW HUSSMANN COM Cove Trim Cement Splashguard...

Страница 14: ...N FLUES MUST REMAIN OPEN AND FREE OF OBSTRUCTION AT ALL TIMES to provide proper refrigeration and air curtain performance Do not allow product packages signs etc to block these grilles Close off curta...

Страница 15: ...nsult your Hussmann representative when in doubt about the effects of third party accessories LOAD LIMITS Shelf life of perishables will be short if load limit is violated AT NO TIME SHOULD CASES BE S...

Страница 16: ...s in Multi deck Merchandisers Return Air Grille Shelf Price Tag Molding Suggested Mounting Locations in Single Deck Glass Front Impact Merchandisers Acrylic Package Guard Facing Out Double Stick Tape...

Страница 17: ...re in the warmest part of a mechan ically refrigerated unit and in the coolest part of a hot FOOD storage unit B Except as specified in C of this section cold or hot holding EQUIPMENT used for POTENTI...

Страница 18: ...or acidic based cleaners on any interior surfaces Coarse paper towels on coated glass Ammonia based cleaners on acrylic parts A hose on rail lights canopy lights or any other electrical connection ST...

Страница 19: ...eycombs 1 Remove interior roof panel to free honey comb 2 Clean and dry the honeycomb 3 After cleaning replace honeycomb and interior roof panel Lower Honeycomb Starting at one lower end of the honeyc...

Страница 20: ...r Fan Plenum Remove the return air grille then remove the screws that hold the plenum and lift out the plenum IMPACT Rear Roll in HUSSMANN CORPORATION BRIDGETON MO 63044 2483 U S A P N 0435045A 5 3 Re...

Страница 21: ...n OR PRODUCT LOSS WILL RESULT due to improper refrigeration REMOVING SCRATCHES FROM BUMPER Most scratches and dings can be removed using the following procedure 1 Use steel wool to smooth out the surf...

Страница 22: ...lade 9 Re install fan mounting panel in coil module 10 Reconnect fan to wiring harness 11 Turn on power Verify that motor is working and blade is turning in the correct direction 12 Ensure the fan ple...

Страница 23: ...are furnished with moisture resistant lamp holders shields and end caps Whenever a fluorescent lamp is replaced be certain to reinstall the lamp shields and end caps The switch in the canopy operates...

Страница 24: ...e light panel at the area where the top of the panel and the top of the case meet pull back and down until the panel swings freely 5 Replace ballast and reassemble parts in reverse order 6 Reconnect t...

Страница 25: ...7 9916 NOTE Hussmann Aluminum melts at 1125 F 607 C Aladdin 3 in 1 rod at 732 F 389 C X Ergon Acid core at 455 F 235 C Technique 1 Locate Leak 2 REMOVE ALL PRESSURE 3 Brush area UNDER HEAT 4 Use PREST...

Страница 26: ...y information or other support contact your Hussmann representative Please include the model and serial number of the product Hussmann Corporation Corporate Headquarters Bridgeton Missouri U S A 63044...

Отзывы: