FAULT INDICATIONS
POSSIBLE CAUSE
REMEDY
Compressor is not
running.
Fuse has blown or a protective
circuit breaker has been
triggered.
Power cord is not plugged in.
Heat regulator setting is too
high.
The cabinet is in the defrosting
cycle.
Replace the fuse or return the
activated protected circuit
breaker.
Insert the power cord plug into a
socket.
Set the heat regulator to a lower
temperature.
Wait till the completion of the
defrosting cycle.
Condensing
unit has been
operating for too
long.
Too much warm food has been
placed in the cabinet.
The cabinet door remains
open or half-open for a long
time.
The door strip is
untight.
Condenser coil is dirty.
Ice formation on the freezer
coil.
Give the food enough time to
cool.
Doors, when not used, should be
closed. Do not leave the doors
open for a long time.
Make sure that the door strip is
firmly fixed. Take the strip off and
rinse it with soapy water.
Check the state of the strip,
replace if needed.
Clean the condenser coil.
Unplug the device and wait until
the coil defrosts. Make sure that
the heat regulator settings are
not too low. Make sure that the
door strip is tight.