UO-EPB-1
Operating and configuration instructions
UO-EPB1_Manual-en_R1
25
Octet
Parameter
Bit no.
Class
when operating
voltage is on
32-35
Drift
23 - 0
Preset value
2
40-43
Configured
resolution
per revolu-
tion
23 - 0
Only if the value
“Resolution per
revolution” has
been entered
2
44-47
Configured
total resolu-
tion
23 - 0
Configured or cal-
culate by scaling
2
48-57
Serial num-
ber
Bytes currently
preset at 2AH
2
6.1 Operating statuses and displays
The status, Net1 and Net2 LEDs are on the front panel of the module housing. They are used to
display the current module status.
6.1.1 Bus status
Net1 red
Net2 green
Error message / bus status
off
off
No power supply
on
on
Wait for configuration by the master (e.g.
incorrect wiring, terminal resistance set
incorrectly)
on
flashing
Coding and/or configuration error (such
as data length too great, total resolution
too high)
on
off
Module receives no signals from the mas-
ter for a long period of time
flashing
on
Module registers data on the bus, but is
not addressed (e.g. wrong address set on
the module)
off
flashing
Commissioning mode in data exchange
mode
off
on
Normal mode in data exchange mode