UPS5000-S-1600 kVA
User Manual
3 Installation
Issue 04 (2020-03-03)
Copyright © Huawei Technologies Co., Ltd.
55
Figure 3-4
Copper bar specifications (unit: mm)
Table 3-2
Recommended cross-sectional areas for power cables
Item
Specifications
Mains input
Mains input current (A)
3046
Bypass input
Bypass input current (A)
2431
Output
Output current (A)
2431
Battery input
Battery nominal discharge current (A)
3509
Battery maximum discharge current (A)
4203
Recommended
cross-sectional area
(mm
2
) for each power
unit
+
3 x (2 x 240)
-
PE
240
Equipotential
ground point
Recommended cross-sectional area
(mm
2
)
16
The currents listed in the tables are measured at a rated voltage of 380 V.
When selecting, connecting, and routing power cables, follow local safety regulations
and rules.
When the external conditions change, for example, the cable layout or ambient
temperatures, perform verification in accordance with the IEC-60364-5-52 or the local
regulations.