UPS5000-S-1600 kVA
User Manual
4 User Interface
Issue 04 (2020-03-03)
Copyright © Huawei Technologies Co., Ltd.
129
Item
Description
Default Value Value Range
Turkish
Password
-
000001
N/A
password
complexity
check
If the password complexity check
is disabled, the user password is
required to be a string of six to
eight digits. If the password
complexity check is enabled, the
password is required to be a
string of 6–20 characters and
contain at least two types of
characters.
Enable
Disable, Enable
Set the date and time as required.
Intelligent Temp Detect
Item
Description
Default
Value
Value Range
Internal
temperature
abnormal alarm
If you set this parameter to
Enable
, an alarm is generated
when the temperature reaches the
preset value.
Enable
Disable, Enable
4.1.3.4 Maintenance
Table 4-18
Maintenance description
Maintenance Item System
Power Unit
Bypass Unit
USB Operations
USB operations
N/A
N/A
Inv. ON
Starting the inverter
of the single UPS
N/A
N/A
Inv. OFF
Shutting down the
inverter of the single
UPS
N/A
N/A
ECM Switchover
Switchover of active
and standby ECMs
N/A
N/A
Screen Calib.
Calibrating the
touchscreen
N/A
N/A
Battery Maint.
N/A
Battery maintenance
of this power unit
N/A