UPS5000-S-1600 kVA
User Manual
3 Installation
Issue 04 (2020-03-03)
Copyright © Huawei Technologies Co., Ltd.
56
If the rated voltage is 400 V, multiply the currents by 0.95. If the rated voltage is 415 V,
multiply the currents by 0.92.
When the primary loads are non-linear loads, increase the cross-sectional areas of the
neutral wires 1.5–1.7 times.
The nominal battery discharge current refers to the current at a voltage of 480 V when
forty 12 V batteries are configured.
The maximum battery discharge current refers to the current when forty 12 V batteries,
that is, two hundred and forty 2 V battery cells (1.67 V/cell), stop discharging.
The battery cable specifications are selected based on 40 batteries and compatible with
application scenarios with 30–50 batteries.
When the mains input and bypass input share a power source, configure input power
cables as mains input power cables. In addition, cables listed in the table apply only to
the following conditions:
−
Routing mode: The cables are routed over a ladder or bracket in a single layer (E in
IEC60364-5-52). The distance between cables should be greater than twice the
cable diameter. Routing mode: The cables are routed over a ladder or bracket in a
single layer (E multi-core and G single-core in IEC60364-5-52).
−
The ambient temperature is 30°C.
−
The AC voltage loss is less than 3%, and the DC voltage loss is less than 1%.
−
90°C flexible copper power cable.
−
It is recommended that the AC power cable be no longer than 30 meters and the DC
power cable be no longer than 50 meters.
When connecting power cables, comply with the tightening torque listed in Table 3-3 to
ensure secure connections and prevent safety risks.
Table 3-3
Power cable terminal requirements
Port
Description
Connection Method
Bolt
Specifications
Bolt Length
Torque
Mains input
Crimped DT terminals
M12
35 mm
47 N·m
Bypass input
Crimped DT terminals
M12
35 mm
47 N·m
Battery input
Crimped DT terminals
M16
55 mm
120 N·m
Output
Crimped DT terminals
M12
35 mm
47 N·m
PE
Crimped DT terminals
M12
35 mm
47 N·m
Equipotential
ground point
Crimped DT terminals
M6
N/A
4.5 N·m
Table 3-4
Recommended upstream input and downstream output circuit breakers
Circuit Breaker Name
Specifications