UPS5000-S-1600 kVA
User Manual
8 Technical Specifications
Issue 04 (2020-03-03)
Copyright © Huawei Technologies Co., Ltd.
191
8
Technical Specifications
Table 8-1
Technical specifications
Item
Specifications
Cabling mode
Battery cables are routed in and out from the top, and input
and output are connected using busbars.
Protection level
IP20
Communication
Supports dry contacts, RS485 ports, and FE ports. Supports
Simple Network Management Protocol (SNMP).
Dimensions (H x W x D)
2200 mm x 4200 mm x 1000 mm
Weight
2800 kg
Table 8-2
Environmental specifications
Item
Specifications
Operating temperature
0°C to 40°C
Storage temperature
–40°C to +70°C
Relative humidity
0%–95% RH (non-condensing)
Altitude
0–1000 m
The power is derated as described in IEC62040-3 when the
altitude is from 1000 m to 4000 m. The upper limit of the
altitude is 4000 m.
Table 8-3
Safety and EMC
Item
Specifications
Safety compliance
CE
EN62040-1: 2013
CB
IEC62040-1: 2013