Parameter Name
Description
Communication
disconnection
detection time
Specifies the time for determining the
communication disconnection
between the SUN2000 and the
Dongle.
This parameter is displayed when
Communication disconnection fail-
safe is set to Enable.
Grid connection
with limited power
(%)
Closed-loop controller
● If multiple SUN2000s are
cascaded, set this parameter to
SDongle/SmartLogger.
● If there is only one SUN2000, set
this parameter to Inverter.
Limitation mode
Total power indicates export
limitation of the total power at the
grid-tied point.
PV plant capacity
Specifies the total maximum active
power in the SUN2000 cascading
scenario.
Maximum grid feed-in
power
Specifies the percentage of the
maximum active power of the grid-
tied point to the PV plant capacity.
Power adjustment
period
Specifies the shortest interval for a
single anti-backfeeding adjustment.
Power control
hysteresis
Specifies the dead zone for adjusting
the SUN2000 output power. If the
power fluctuation is within the power
control hysteresis, the power is not
adjusted.
Active power output
limit for fail-safe
Specifies the derating value of the
SUN2000 active power by percentage.
If the Smart Dongle does not detect
any meter data or the
communication between the Smart
Dongle and the SUN2000 is
disconnected, the Smart Dongle
delivers the derating value of the
SUN2000 active power by percentage.
SUN2000-(2KTL-6KTL)-L1
User Manual