SUN2000-(25KTL, 30KTL)-US
User Manual
5 Electrical Connections
Issue 03 (2017-04-01)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
61
connected
(3) Neutral wire not connected, PE wire
connected
(4) Neutral wire and PE wire connected
----End
5.5 Connecting DC Input Power Cables
Connect the SUN2000 to PV strings over DC input power cables.
Prerequisites
Before connecting DC input power cables, ensure that the voltage on the DC side is within
the safe range (lower than 60 V DC) and that the
DC SWITCH
on the SUN2000 is
OFF
.
Otherwise, high voltage may result in electric shock.
When the SUN2000 is grid-tied, do not maintain DC input power cables, such as
connecting or disconnecting a PV string or a PV module in a PV string. Otherwise, it may
result in electric shocks.
To avoid fire, ensure that the following conditions are met.
The maximum open-circuit voltage of each PV string must be always lower than or equal
to 1000 V DC.
The positive and negative terminals of PV modules must be connected to the positive and
negative DC input terminals of the SUN2000 respectively.