FusionModule1000A20 Prefabricated All-in-One Data
Center
Installation Guide
A A Basic Installation Operations
Issue 02 (2020-01-15)
Copyright © Huawei Technologies Co., Ltd.
83
Figure A-1
Cable ties without sharp burs
Figure A-2
Cable ties in the same direction
Bending Cables
When bending cables, observe the following rules:
Cables must not be overly bent because over bending may damage the cable cores.
The bending radius of a cable must be more than twice the cable diameter. The bending
radius near a connector outlet must be more than four to six times the cable diameter.
Cables must not be tied where they bend.
Figure A-3
Binding cables at a turning point
A.1.2 Measuring Cables
Prerequisites
Pre-fab. modules have been installed.
External cable trays have been installed.