FusionModule1000A20 Prefabricated All-in-One Data
Center
Installation Guide
4 Installing Pre-fab. Modules
Issue 02 (2020-01-15)
Copyright © Huawei Technologies Co., Ltd.
30
Procedure
Step 1
Secure the ground lugs to the pre-fab. module ground points by tightening M12x30 stainless
steel bolt assemblies.
Before the installation, remove the tinfoil from the ground lugs.
Figure 4-15
Installing a ground lug
In addition to using ground lugs, you can also connect ground cables to pre-fab. module ground points
using M12x30 stainless steel bolt assemblies, as shown in the following figure. Ground cables can be
routed through plastic-coated metal hoses for protection based on site requirements.
Figure 4-16
Installing a ground cable
----End