FusionModule1000A40 Prefabricated All-in-One Data
Center
Installation Guide
2 Site Requirements
Issue 03 (2020-06-09)
Copyright © Huawei Technologies Co., Ltd.
7
The pre-fab. module must be located in an area with proper drainage. To prevent ponding
which may affect equipment operation, deploy drainage channels before constructing a
concrete foundation.
Dispose of drainage water in accordance with local laws and regulations.
Anti-freezing measures must be applied for pipes in low-temperature areas.
2.5.3 Pipe Anti-freezing
Condensate drainpipes of air conditioners and water refill pipes of humidifiers may freeze and
thereby be blocked or crack in low-temperature areas. Anti-freezing measures must be taken
for the pipes.
Wrap the pipes with an electric heating belt, starting from the water refill and drainage ports
on a pre-fab. module to the frozen soil layer. Bury the remaining pipes underground (the
temperature at a specific depth underground is always above 0°C).
Figure 2-4
Pipe anti-freezing solution
(1) Trap
(2) Electric heating belt
(3) Water refill pipe
(4) Drainpipe
(5) Soil