FusionModule1000A40 IT Solution
Maintenance Guide (2016.05, AI Version)
5 Components Replacement
Issue 04 (2018-01-05)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
102
Figure 5-27
Connecting cables
Step 5
Reinstall the baffle plate.
Step 6
Check that the new electronic lock is working properly.
If the electronic lock indicator is green when the pre-fab. module door is closed and red when the door is
open, the electronic lock is working properly.
----End
Follow-up Procedure
Dispose of the removed electronic lock that is confirmed faulty.
5.3.8.5 Replacing an Emergency Door Release Button
Prerequisites
The emergency door release button needs to be replaced.
A spare emergency door release button of the same model is available and functional.
Impact on the System
None
Preparations
Tools: insulation tape, step ladder (2 m), Phillips screwdriver, protective gloves
Materials: spare emergency door release button
Document: none
Skill requirement: weak-current engineer
Procedure
Step 1
Remove the emergency door release button.