Table 2-5.7: HTW-V16WD2N8 heating capacity - peak values
1
Outdoor air temp.
LWT (⁰C)
30
35
40
45
50
55
60
⁰C DB
⁰C WB
HC
PI
COP HC
PI
COP HC
PI
COP HC
PI
COP HC
PI
COP HC
PI
COP
HC
PI
COP
-25.0
-
6.8 2.1 3.20 6.6 2.9 2.29
-20.0
-
8.6 2.2 3.93 8.5 3.0 2.78 8.3 3.8 2.18
-15.0
-
10.5 2.5 4.16 10.2 3.2 3.21 9.9 4.1 2.38 9.5 5.2 1.85 9.2 5.3 1.75
-7.0
-8.0
13.5 2.7 4.91 13.0 3.5 3.75 12.5 4.2 3.00 12.1 4.9 2.48 11.6 5.6 2.09 11.2 6.2 1.80 10.8 6.9 1.56
-2.0
-3.0
15.7 3.0 5.28 15.0 3.6 4.15 14.4 4.3 3.38 13.7 4.9 2.82 13.1 5.5 2.40 12.5 6.1 2.07 11.9 6.6 1.80
2.0
1.0
20.7 3.4 6.17 19.3 3.9 4.94 17.9 4.4 4.06 16.6 4.9 3.39 15.3 5.3 2.87 14.1 5.8 2.45 12.9 6.1 2.10
7.0
6.0
16.6 3.2 5.18 16.3 3.7 4.45 15.9 4.1 3.88 15.6 4.6 3.42 15.2 5.0 3.04 14.9 5.5 2.73 14.5 5.9 2.46
15.0
12.0
18.1 2.7 6.64 17.7 3.1 5.71 17.3 3.5 4.97 16.9 3.9 4.39 16.5 4.2 3.90 16.2 4.6 3.50 15.8 5.0 3.16
20.0
15.0
17.7 2.4 7.44 17.3 2.7 6.39 17.0 3.0 5.57 16.6 3.4 4.91 16.2 3.7 4.37 15.8 4.0 3.92 15.5 4.4 3.54
25.0
18.0
16.4 2.0 8.12 16.1 2.3 6.98 15.7 2.6 6.08 15.4 2.9 5.36 15.0 3.1 4.77 14.7 3.4 4.28 14.3 3.7 3.86
30.0
22.0
14.2 1.6 8.65 13.9 1.9 7.43 13.6 2.1 6.47 13.3 2.3 5.71 13.0 2.6 5.08 12.7 2.8 4.56 12.4 3.0 4.11
35.0
24.0
11.0 1.2 8.89 10.7 1.4 7.64 10.5 1.6 6.66 10.3 1.8 5.87 10.0 1.9 5.22 9.8 2.1 4.68
Abbreviations:
LWT: Leaving water temperature (°C )
HC: Total heating capacity (kW)
PI: Power input (kW)
Notes:
1. Peak heating capacity values do not take account of capacity drops caused by frost accumulation and during defrosting.
Table 2-5.8: HTW-V16WD2N8 heating capacity - integrated values
1
Outdoor air temp.
LWT (⁰C)
30
35
40
45
50
55
60
⁰C DB
⁰C WB
HC
PI
COP HC
PI
COP HC
PI
COP HC
PI
COP HC
PI
COP HC
PI
COP HC
PI
COP
-25.0
-
6.1 2.1 2.88 5.9 2.7 2.16
-20.0
-
7.7 2.2 3.53 7.5 2.9 2.61 7.4 3.6 2.05
-15.0
-
9.4 2.3 4.07 9.2 3.0 3.02 9.0 3.8 2.38 8.8 4.5 1.95 8.6 5.2 1.64
-7.0
-8.0
12.0 2.6 4.70 11.8 3.3 3.60 11.5 4.0 2.90 11.3 4.7 2.41 11.0 5.4 2.05 10.8 6.1 1.77 10.5 6.8 1.55
-2.0
-3.0
13.7 2.8 4.95 13.4 3.4 3.93 13.1 4.1 3.23 12.8 4.7 2.73 12.5 5.3 2.35 12.2 6.0 2.04 11.9 6.6 1.80
2.0
1.0
15.0 2.9 5.08 14.7 3.5 4.17 14.4 4.1 3.51 14.0 4.7 3.01 13.7 5.2 2.62 13.4 5.8 2.31 13.1 6.4 2.06
7.0
6.0
16.6 3.2 5.18 16.3 3.7 4.45 15.9 4.1 3.88 15.6 4.6 3.42 15.2 5.0 3.04 14.9 5.5 2.73 14.5 5.9 2.46
15.0
12.0
18.1 2.7 6.64 17.7 3.1 5.71 17.3 3.5 4.97 16.9 3.9 4.39 16.5 4.2 3.90 16.2 4.6 3.50 15.8 5.0 3.16
20.0
15.0
17.7 2.4 7.44 17.3 2.7 6.39 17.0 3.0 5.57 16.6 3.4 4.91 16.2 3.7 4.37 15.8 4.0 3.92 15.5 4.4 3.54
25.0
18.0
16.4 2.0 8.12 16.1 2.3 6.98 15.7 2.6 6.08 15.4 2.9 5.36 15.0 3.1 4.77 14.7 3.4 4.28 14.3 3.7 3.86
30.0
22.0
14.2 1.6 8.65 13.9 1.9 7.43 13.6 2.1 6.47 13.3 2.3 5.71 13.0 2.6 5.08 12.7 2.8 4.56 12.4 3.0 4.11
35.0
24.0
11.0 1.2 8.89 10.7 1.4 7.64 10.5 1.6 6.66 10.3 1.8 5.87 10.0 1.9 5.22 9.8 2.1 4.68
Abbreviations:
LWT: Leaving water temperature (°C )
HC: Total heating capacity (kW)
PI: Power input (kW)
Notes:
1. Integrated heating capacity values take account of capacity drops caused by frost accumulation and during defrosting.