HTW
-V16WD2RN8
Table 2-1.
4
:
HTW
-V16WD2RN8 specifications
1
kW
16
Model name
HTW-V16WD2RN8
Power supply
V/Ph/Hz
380-415/3/50
Heating
2
Capacity
kW
16.30
Rated input
kW
3.63
COP
4.49
Heating
3
Capacity
kW
16.20
Rated input
kW
4.70
COP
3.45
Heating
4
Capacity
kW
16.10
Rated input
kW
5.83
COP
2.76
Cooling
5
Capacity
kW
15.50
Rated input
kW
3.63
EER
4.27
Cooling
6
Capacity
kW
13.80
Rated input
kW
5.19
EER
2.66
Seasonal space heating
energy efficiency class
7
LWT at 35⁰C
A++
A++
A++
LWT at 55⁰C
A++
A++
A++
SCOP
7
LWT at 35⁰C
4.30
LWT at 55⁰C
3.27
SEER
7
LWT at 7⁰C
4.54
LWT at 18⁰C
6.78
Compressor
Type
Twin rotary DC inverter
Poles
6
6
6
Speed range
rps
10-102
12-120
12-120
Capacity at 60rps
kW
13.38
Input at 60rps
kW
4.40
Max. heating
frequency
Hz
92
92
92
Max. cooling
frequency
Hz
78
78
78
Outdoor fan
Motor type
Brushless DC motor
Number of fans
2
2
2
Air flow
m
3
/h
6150
6250
6250
Air side heat exchanger
Type
Finned tube
Number of rows
2
2
2
Number of circuits
9
9
9
Abbreviations:
MOP: Maximum overcurrent protection
MCA: Minimum circuit amps
DHW: Domestic hot water
EWT: Entering water temperature
LWT: Leaving water temperature
Notes:
1. Relevant EU standards and legislation: EN14511:2013; EN14825:2013; EN50564:2011; EN12102:2011;
(EU) No 811/2013; (EU) No 813/2013; OJ 2014/C 207/02.
2. Outdoor air temperature 7⁰C DB, 85% R.H.; EWT 30⁰C, LWT 35⁰C.
3. Outdoor air temperature 7⁰C DB, 85% R.H.; EWT 40⁰C, LWT 45⁰C.
4. Outdoor air temperature 7⁰C DB, 85% R.H.; EWT 47⁰C, LWT 55⁰C.
5. Outdoor air temperature 35⁰C DB; EWT 23⁰C, LWT 18⁰C.
6. Outdoor air temperature 35⁰C DB; EWT 12⁰C, LWT 7⁰C.
7. Seasonal space heating energy efficiency class tests in average climate conditions.
8. Sound power level is the maximum value tested under the three conditions of Notes1, Notes3 and Note5.
Table continued on next page …