PVCHECK
12
5.2.
EFF
– EFFICIENCY TEST SETTINGS FOR PV INSTALLATIONS
The purpose of this measurement is to evaluate the DC efficiency of a photovoltaic
installation, with the possibility of obtaining a positive or negative result of the
check/recording depending on a limit on the
nDC
parameter, freely set by the user.
For this
test, the use of the optional remote unit SOLAR-02 is necessary
(see § 6.1)
5.2.1. Instrument settings
1. Position the cursor onto
EFF
by using the arrow keys
and confirm with
ENTER
. The display shows the values of the
output electrical parameters of the photovoltaic generator.
2. Press the
ENTER
key. The instrument shows the following
options:
System parameters
and
Instrument settings
.
3. Use the arrow keys
to select “
Instrument settings
”
and confirm with
ENTER
. The instrument shows the following
screen:
cursor onto
EFF
by using the arrow keys
4. By using the arrow keys
it is possible to set:
The integration period (IP) which can be used by the
instrument when testing the parameters of a PV system.
The following values can be selected:
5s, 10s, 30s, 60s,
120s, 300s, 600s, 900s, 1800s, 3600s
.
The FS of the DC clamp used for measuring DC current
with value selectable between
1A
3000A
5. Press the
SAVE
key to save the settings made; the message
“Data saved” will be displayed for a few seconds. Press the
ESC/MENU
key to exit without saving and go back to the
previous screen.
(
Содержание PVCHECK
Страница 1: ...Manual PVCHECK EAN 8033772797467...
Страница 2: ...PVCHECK 2 PVCHECK...
Страница 56: ...v 181002 2018 10 02 11 20...