23
”Service menu”:
”Service menu”
Text
Default
values
Min. value
Max.
value
Explanation
Extra sensor
OFF, hot water, storage tank
OFF
-
-
Selection
of
function
for
extra
temperature sensor
Extra pump function
Circ. pump, boiler pump
Boiler-
pump
-
-
Selection of function for pump
Boiler parameters
Min. temperature
65 °C
40 °C
78 °C
Min. set point for boiler temperature
Max. temperature 1)
85 °C
78 °C
94 °C
Set point for temperature in hot water
tank
Overheat
95 °C
86 °C
99 °C
Max. boiler temperature – higher temp.
sets off an alarm
Hysteresis
10 °C
1 °C
20 °C
Necessary fall in boiler temperature
before re-start is possible.
Circuit pump *)
Start pump
52 °C
40 °C
70 °C
Boiler temperature at which the boiler
temperature should start
Hysteresis
2 °C
1 °C
10 °C
Number of degrees less than pump start
temperature at which pump should stop
Cyclic
No
No
Yes
The
pump
can
either
operate
continuously or cyclic.
Switching frequency **)
5 min
1 min
240 min
Time when pump is either ON or OFF
Low output
Fan delay
15 sec
1 sec
200 sec
Delay in fan speed change when switching
to low output.
Hysteresis
5 °C
1 °C
20 °C
Number of degrees less than the set point
at which a change-over to low load occurs
with increasing boiler temperature
High output
Fan delay
15 sec
1 sec
200 sec
Delay in change of fan speed at change to
high output.
Hysteresis
10 °C
1 °C
20 °C
Number of degrees less than the set point
at which a change-over to high load
occurs
with
decreasing
boiler
temperature
Ignition
Max. ignition time
6 min
1 min
30 min
Time-out in case of ignition attempts
Max. number of attempts
2
1
10
Max. number of extra ignition attempts
Cleaning time
30 sec
1 sec
200 sec
Pre-ventilation of burner before start of
ignition
Burn out
Burn out time
15 sec
1 sec
900 sec
Fan run time after shut down
Burner auger
Burner auger
ON
ON
OFF
-
Run time at stop
20 sec
1 sec
200 sec
Required time for removing fuel out of
the internal auger
Pause
3 sec
2 sec
200 sec
Pause internal auger
Cycle
2 sec
1 sec
3 sec
Run time internal auger
Feeder auger
Filling time
3 min
0 min
30 min
Required time for filling the feeder auger
Light sensor
Measurement frequency
1 Hz
1 Hz
10 Hz
Measurement frequency for light sensor
Hysteresis
15
0
99
Required increase above minimum of light
value before ignition stops after start.
Cleaning
Cleaning
OFF
ON
OFF
Only to be ON if automatic cleaning
system is available.
Cooling time
60 sec
1 sec
200 sec
Pre-ventilation of burner before cleaning
starts
Opening time
3 min
1 min
20 min
Cleaning time
Quantity of burnt out material
5
0
100
Number of shut downs between cleanings
On min
0 h
0 h
4 h
Shortest time in hours between cleanings
On max
4 h
4 h
100 h
Longest time between cleanings
Not earlier than
07.00
00.00
Latest
Cleaning must not take place before this
hour
Latest
21.00
Not earlier
than
24.00
Cleaning must not take place after this
hour
Default settings
Back to factory settings.
-
Yes
No
-
Test outputs
2)
-
-
-
-
Test inputs
3)
-
-
-
-
Language
Language Danish
Polish,
English,
German
and Danish
-
1) Operation with storage tank: The max. temperature decides when the burner stops if the boiler gets hotter than the storage tanks.
2) and 3): see next page
*) only active when circuit pump is selected; **) only active when ”cyclic” is set to Yes.