Shenzhen Hpmont Technology Co., Ltd
Appendix A Parameters
HD20 Series Inverters User Manual
-
123
-
No.
Name
Range
Factory
Default
Unit
Modified
attributes
Setting
EEPROM parameter 2 to the
current function code settings
(including the motor
parameters).
F01.03
Display panel EEPROM
parameter initialization
0: No operation
1: Upload the current function
code settings to the display
panel EEPROM parameter 1
2: Upload the current function
code settings to the display
panel EEPROM parameter 2
0
1
○
Group F02 Run/Stop Control Parameters (refer to pages 56
F02.00 Start mode selection
0: From the DWELL frequency
to start
1: Brake first and then start
from DWELL frequency
2: Start after speed tracking. If
the result of speed tracking is
smaller than F02.02, it will start
from the starting DWELL
frequency
0
1
×
F02.01 Starting delay time
0.00
-
10.00s
0.00s
0.01s
×
F02.02
Start DWELL frequency
setting
0.00
-
upper limit
0.00Hz
0.01Hz
×
F02.03
Retention time of starting
DWELL frequency
0.00
-
10.00s
0.00s
0.01s
×
F02.04 DC braking current setting
0
-
100% (inverter’s rated
current)
50%
1%
×
F02.05 DC braking time at start
0.00
-
60.00s
0.50s
0.01s
×
F02.06 Reserved
F02.07
Speed search mode
based on current
0: From the max. output
frequency to start speed
searching
1: From at stop moment
frequency to start speed
searching
1
1
×
F02.08
Setting reference current
for speed search
0
-
100% (motor’s rated
current)
50%
1%
×
F02.09
Acc./Dec. time of the
speed search
1.0
-
50.0s
5.0s
0.1s
×
F02.10
Waiting time of speed
search
0.1
-
5.0s
1.0s
0.1s
×
F02.11 V/f ratio of speed search
0.0
-
100.0%
100.0%
0.1%
×
F02.12
Disposal time after speed
search
0.01
-
5.00s
1.00s
0.01s
×
F02.13 Stop mode selection
0: Decelerate to stop
0
1
×
A