Shenzhen Hpmont Technology Co., Ltd
Chapter 6 Function Introduction
HD20 Series Inverters User Manual
―
105
―
Fault history (F20.21
-
F20.37)
F20.22
-
F20.29 record the inverter status parameters at the last fault.
F20.30
-
F20.37 record the type and interval per time of four faults before the last. The interval’s
unit is 0.1 hour.
No.
Name Description
Range
【
factory setting
】
F20.21
Type of fifth latest (the last) fault
【
actual value
】
F20.22
Setting frequency at the last fault
F20.23
Running frequency at the last fault
F20.24
Bus voltage at the last fault
F20.25
Output voltage at the last fault
F20.26
Output current at the last fault
F20.27
Input terminal status at the last fault
F20.28
Output terminal status at the last fault
F20.29
Interval of fifth latest fault
F20.30
Type of fourth latest fault
F20.31
Interval of fourth latest fault
F20.32
Type of third latest fault
F20.33
Interval of third latest fault
F20.34
Type of second latest fault
F20.35
Interval of second latest fault
F20.36
Type of first latest fault
F20.37
Interval of first latest fault
6.2.22 Group F21 Reserved
6.2.23 Group F22 Reserved
6.2.24 Group F23 PWM Control Parameters
No.
Name Description
Range
【
factory setting
】
F23.00
Set the carrier frequency
1
-
16
【
8kHz
】
F23.00 defines the carrier frequency of PWM output wave.
• The carrier frequency will affect the operating noise of the motor. The higher the carrier frequency,
the lower the noise made by the motor. Please properly set the carrier frequency.
• When the value is higher than the factory setting, the inverter should be derated by 5% when per
1kHz is increased compared to the factory setting.
F23.01
Reserved
F23.02
PWM overshoot enable
0,1
【
1
】
0: Disabled.
1: Enabled.
6.3 Group y Manufacturer Function Parameters
The Group y is the manufacturer parameters group for debugging at the factory before delivery.