Appendix A Parameters
Shenzhen Hpmont Technology Co., Ltd
―
120
―
HD20 Series Inverters User Manual
No.
Name
Range
Factory
Default
Unit
Modified
attributes
Setting
d00.43 Reserved
d00.44 Process PID reference
-100.0
-
100.0%
*
d00.45 Process PID feedback
-100.0
-
100.0%
*
d00.46 Process PID tolerance
-100.0
-
100.0%
*
d00.47 Process PID integral item
-100.0
-
100.0%
*
d00.48 Process PID output
-100.0
-
100.0%
*
d00.49 External counting value
0
-
9999
*
d00.50 Input terminal status
Bit0
-
Bit8 corresponding to
DI1
-
DI9
Bitx: DIy terminals input
positive and negative logic
0: Positive logic
1: Negative logic
*
d00.51 Output terminal status
Bit0
-
Bit1 corresponding to
DO1
-
DO2
Bit2
-
Bit11 corresponding to
RLY1
-
RLY10
Bitx: DOy, RLYy terminals
output positive and negative
logic
0: Positive logic
1: Negative logic
*
d00.52
MODBUS communication
status
0: Normal
1: Communication timeout
2: Incorrect data frame head
3: Incorrect data frame
checking
4: Incorrect data frame content
*
d00.53 Actual length
0
-
65535m
*
d00.54 Total length
0
-
65535km
*
d00.55 Total time at power-on (h)
0
-
65535h
*
d00.56 Total time at operation (h)
0
-
65535h
*
d00.57
High bit of motor total
energy consumption
0
-
65535k kW.h
*
d00.58
Low bit of motor total
energy consumption
0.0
-
999.9kW.h
*
d00.59
High bit of energy consum.
at this time running
0
-
65535k kW.h
*
d00.60
Low bit of energy consum.
at this time running
0.0
-
999.9kW.h
*
d00.61 Fault at the moment
1
-
99
*
Group F00 Basic Parameter (refer to pages 52
F00.00 Reserved
F00.01 Control mode selection
0: V/f control without PG
0
1
×