Hoval UltraOil 50 Скачать руководство пользователя страница 21

4 210 256 / 01 

21

Commissioning

Heating Water

The European Standard EN 14868 and the 

directive VDI 2035 must be observed.

In particular, attention must be paid to the following stipu-

lations:

•  Hoval boilers and calorifi ers are designed for heating 

plants without signifi cant oxygen intake (plant type I ac-

cording to EN 14868).

• 

Plants with

 -

continuous  oxygen  intake  (e.g.  underfloor  heating 

systems without diffusion proof plastic piping) or

 -

intermittent oxygen intake (e.g. where frequent refill-

ing is necessary)

must be equipped with 

separate circuits.

•  Treated fi lling and replacement water must be tested at 

least 1x yearly. According to the inhibitor manufacturer‘s 

instructions, more frequent testing may be necessary.

•  A refi lling is not necessary if the quality of the heating 

water in existing installations (e.g. exchange of boiler) 

conforms to VDI 2035.

The Directive VDI 2035 applies equally to the replace-

ment water.

•  New and if applicable existing installations need to be 

adequately cleaned and fl ushed befor being fi lled. The 

boiler may only be fi lled after the heating system has 

been fl ushed!

•  Parts of the boiler / calorifi er which have contact with 

water are made of ferrous materials and stainless steel.

• 

On account of the danger of stress cracking corrosion 

in the stainless steel section of the boiler the chloride, 

nitrate and sulphate content of the heating water must 

not exceed 50 mg/l.

• 

The pH value of the heating water should lie between 

8.3 and 9.5 after 6-12 weeks of heating operation.

Filling and replacement water

• 

For a plant using Hoval boilers untreated drinking water 

is generally best suited as heating medium, i.e. as fi ll-

ing and replacement water. However, as not all drinking 

water is suitable for use as as fi lling and replacement 

water  the  water  quality  must  fulfi l  the  standard  set  in 

VDI 2035. Should the mains water available not be 

suited for use then it must be desalinated and/ or be 

treated  with  inhibitors.  The  stipulations  of  EN 14868 

must be observed.

•  In order to maintain a high level of boiler effi ciency and 

to avoid overheating of the heating surfaces the values 

given in the table should not be exceeded (dependent 

on boiler performance ratings - for multi-boiler plants 

rating of smallest boiler applies - and on the water con-

tent of the plant).

•  The total amount of fi lling and replacement water which 

is used throughout the total service life of the boiler 

must not exceed three times the water capacity of the 

plant.

Maximum filling capacity based on VDI 2035

Total hardness of the fi lling water up to ...

[mol/m

3

1

<0,1

0,5

1

1,5

2

2,5

3

>3,0

f°H

<1

5

10

15

20

25

30

>30

d°H

<0,56

2,8

5,6

8,4

11,2

14,0

16,8

>16,8

e°H

<0,71

3,6

7,1

10,7

14,2

17,8

21,3

>21,3

~mg/l

<10

50,0

100,0

150,0

200,0

250,0

300,0

>300

Conductance 

2

<20

100,0

200,0

300,0

400,0

500,0

600,0

>600

Boiler size of the 

individual boiler

maximum fi lling quantity without desalination

to 50 kW

NO REQUIREMENT

20 l/kW

Sum of alkaline earths

If the conductance in µS/cm exceeds the tabular value an analysis of the water is necessary.

5. Commissioning

5.1  Water quality

Содержание UltraOil 50

Страница 1: ...closed circuits but is equally suitable for installation in open circuits 1 see chapter 3 2 Hoval products must be installed and commissioned only by appropriately qualified experts These instruc tion...

Страница 2: ...ney 14 4 2 1 Exhaust gas flues approved by building re gulations 15 4 2 2 Example of an exhaust gas flue 15 4 2 3 Project planning instructions 15 4 2 4 Dimensioning flue gas system 15 4 3 Fuel 16 4 4...

Страница 3: ...r and burner cleaning 26 6 2 2 Re assembly of the boiler 26 6 3 Cleaning the combustion chamber and the aluFer pipes 28 Leakage testing 28 6 4 Servicing the neutralisation installation if fitted 29 Pr...

Страница 4: ...use chimneys requirements plan ning and execution PED Pressure Equipment Directive TRD 721 Safety equipment to safeguard against excess pressures safety valves for group II steam boilers VDI 2035 Prev...

Страница 5: ...transport up and down stairs it is wise to leave these timbers in place under the boiler A special foundation plate for the boiler is not an es sential but it is recommended Space required The flange...

Страница 6: ...wer drain line Drain optionally on the left or right side 1 3 2 Possibility 2 Design with neutralisation box For condensate discharge in lower drain line incl condensate neutralisation 1 3 2 Possibili...

Страница 7: ...o so loosen the screw 6 fig 02 and rotate the burner by 15 The required Allen key 5 is supplied with the burner 5 6 Fig 02 7 Mount the burner flange including sealing to the boiler flange in accordanc...

Страница 8: ...er to prevent it falling out figure 06 Fireproof fibre Fig 06 10 Close the boiler flange with the burner once again 11 The oil feeds may be taken through the side openings either on the right or the l...

Страница 9: ...08 9 Fig 09 13 Connect up the pipes 9 fig 09 Tip to help assembly put the pipe in place and twist it slightly 14 Reattach the side walls 4 fig 01 locking screws 3 lid 2 and front cover 1 Further infor...

Страница 10: ...and standards We hereby declare that the product described as an individual appliance complies with the standards guidelines and technical specifications laid down Directives 92 42 EG Boiler efficienc...

Страница 11: ...ated heating capacity 12 5 CO2 500 m over sea level tolerance 20 mbar 0 75 Quantity of condensate at 40 30 C l h 3 52 Flow resistance of boiler 1 zeta value 1 50 Water side resistance at 10 K mbar 27...

Страница 12: ...ature return R1 3 Leadthrough for oil feed left or right 4 LAS flue gas supply air connection C100 150 5 Boiler control 6 Condensation drainage left or right including siphon DN25 and 2 m PVC pipe inn...

Страница 13: ...oor incl burner swivels upwards and to the left or to the front A minimal 150 mm Burner service position front boiler cleaning from the right A optimal 300 mm Burner service position left boiler clean...

Страница 14: ...nd chimney The exhaust system must be gastight water tight resistant to acids and be approved for the corresponding ex haust gas temperatures up to 120 C and for operation at pressure Horizontal conne...

Страница 15: ...ing must be through tested and approved exhaust gas pipework The exhaust gas pipework must be gastight wa tertight resistant to corrosion and acids and ap proved for use with exhaust gas temperatures...

Страница 16: ...f tank volume Residual amount heating oil EL sulphur content 1000 ppm resp 0 1 max 5 of tank volume Residual amount eco heating oil EL sulphur content 500 ppm resp 0 05 max 10 of tank volume In order...

Страница 17: ...remove to wards the front 4 Remove the locking screw 4 on the right 5 Lift the switch control box 5 and fold it out Theelectricalconnectionistobemadeinaccordance with the diagram supplied 4 4 Electric...

Страница 18: ...rference may be connected nor may it be possible to make such a connection Cut out Boiler room emergency switch Heater Boiler room lighting and sockets to be connected to a separate circuit 3 The exte...

Страница 19: ...rs Flow 40 C Return flow 30 C Flow 80 C Return flow 60 C kW heating output C exhaust gas temperature using heating oil EL CO2 12 5 C 60 70 80 90 100 30 40 50 28 29 30 31 32 33 34 35 36 37 38 39 40 41...

Страница 20: ...4 9 Safety valves The heating equipment and hot water system must be protected with one safety valve each against unau thorisedhighpressures Theirblowingoffperformance must correspond with the boiler...

Страница 21: ...r should lie between 8 3 and 9 5 after 6 12 weeks of heating operation Filling and replacement water For a plant using Hoval boilers untreated drinking water is generally best suited as heating medium...

Страница 22: ...ox where fitted is to be filled with water 5 5 Oil burner Setting the burner must also be carried out by the installing engineer and must correspond to the heat requirement of the plant For this purpo...

Страница 23: ...H Gen without minimum H Gen temperature e g condensing boiler Start PRESS HC level Parameters 13 16 H GEN level Parameter 4 Characteristic heating curve Enable HC Activate Installer level Code entry...

Страница 24: ...6 17 18 19 20 21 22 23 24 25 26 t TAGE 55 45 35 25 Funktionsheizen und Belegreifheizen START 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 TAGE 55 45 35 25 3 Funktionsheizen und...

Страница 25: ...s metering Immediate end PRESS SHORTLY Remaining time display REACTIONS for emissions metering Time unit automatically 20 min thereafter reverts Boiler temperature maximum temperature restriction Regu...

Страница 26: ...fting it straight up wards and off Undo the burner plug connections burner cable cable remote control unlocking Remove the corrugated pipe from the burner air intake adapter Undo the locknuts 6 Draw t...

Страница 27: ...4 210 256 01 27 Maintenance 2 8 9 7 1 4 10 Fig 14 6 5 3...

Страница 28: ...dirt particles must be adequately rinsed out of the condensate drip tray Do not use wire brushes or any sharp objects for cleaning Ensure that the combustion chamber does not come into contact with ir...

Страница 29: ...he front cover Undo the bolts and withdraw the neutralisation box Remove the neutralisation granules and any deposits from the neutralisation box Any remaining neutralisa tion granulate since it is ha...

Страница 30: ...son for the excessive exhaust gas temperature must be established by the installation engineer Possible causes are excessive contamination of the heating surface burner output set too high Boiler wate...

Страница 31: ...e target temperature HC 20 C 5 30 C Daytime target temperature MC1 20 C 5 30 C Daytime target temperature MC2 20 C 5 30 C Night time target temperature HC 16 C 5 30 C Night time target temperature MC1...

Страница 32: ...2 Cycle 3 Cycle 1 Cycle 2 Cycle 3 from to from to from to from to from to from to from to from to from to Mo Tu We Th Fr Sa Su Mixer Circuit 1 Time program P1 Time program P2 Time program P3 Tag Cycl...

Страница 33: ...1 HF 4 Limit temperature for summer disconnection 22 C HF 5 System frost protection 3 C HF 6 Demand contact module for VE1 1 HF 7 Demand contact module for VE2 1 HF 8 Demand contact module for VE3 1...

Страница 34: ...me out OFF 30 min HF 20 PI reference value control OFF HF 21 PI amplification factor P portion Xp 0 1 K OEM 22 PI scanning time Ta 20 s OEM 23 PI reset time Tn 600 s C OEM UNMIXED CIRC Par Designation...

Страница 35: ...tion abatement heating circuit 0 8 K HF 15 Pump follow on 5 min HF 16 Screed function OFF HF 18 P portion Xp 2 0 K OEM 19 Scanning time Ta 20 s OEM 20 I portion Tn 270 s OEM 21 Running time servomotor...

Страница 36: ...tion abatement heating circuit 0 8 K HF 15 Pump follow on 5 min HF 16 Screed function OFF HF 18 P portion Xp 2 0 K OEM 19 Scanning time Ta 20 s OEM 20 I portion Tn 270 s OEM 21 Running time servomotor...

Страница 37: ...K OEM 20 Modulation scanning time Ta 20 s OEM 21 Modulation adjustment time Tn 180 s C OEM 22 Modulation running time 12 s HF 23 Modulation starting time 200 s HF 24 Modulation start up output 70 HF...

Страница 38: ...on 2 HF 7 Heat generator cycle lock only when parameter 06 1 3 4 0 5 h HF 8 Solar priority parallel changeover 10 K HF 9 Solar heat balance OFF HF SOLAR RESET Reset heat balance HF 11 Volumetric flow...

Страница 39: ...Par Designation Factory 10 20 30 40 50 Lev 1 Bus address central device 10 HF 2 Bus right RS direct circuit 1 HF 3 Bus right RS mixer circuit 1 1 HF 4 Bus right RS mixer circuit 2 1 HF BUFFER Par Des...

Страница 40: ...MAINTENANCE ST 1 for X days 7 HF 12 Maintenance according to fixed date OFF HF 13 Maintenance according to fixed interval OFF HF 14 Maintenance according to maintenance counter OFF HF 15 Reset mainte...

Страница 41: ...on KVLF 19 0 System Collector sensor Short circuit KVLF 19 1 System Room sensor RS Interruption 20 0 System Room sensor RS Short circuit 20 1 System Burner 1 No switching off 1 min 30 2 With par log a...

Страница 42: ...tpoint 85 4 System HP return sensor Return max temp exceeded 85 5 System QF Heat source min temp below setpoint 86 4 System QF Heat source max temp exceeded cooling operation 86 5 System QF Fault heat...

Страница 43: ...4 210 256 01 43...

Страница 44: ...ype Serial number Year of manufacture Place Date System installer System user Confirmation The user owner of the system herewith con rms that he has received adequate instruction in the operating and...

Отзывы: