Parameter
Description
Unit
Level
System set values
45 - UG (15)
45 - UG (20)
45 - UG (27)
45 - UG (35)
45 -
UG (50)
31
2FJ
32799
Upward ramp of the fan during venting
min
–1
/s
OEM
500 500 500 500 500
32
2FK
32800
Downward ramp of the fan during venting
min
–1
/s
OEM
200 200 200 200 200
33
2FL
32801
Upward ramp of the fan during operation
min
–1
/s
OEM
100 100 100 100 100
34 2FM 32802
Downward ramp of the fan during operation
min
–1
/s
OEM
100 100 100 100 100
35
2FN
32803
Post-venting of the fan after lock-out
sek
OEM
180 180 180 180 180
36
2FO
32804
Fan speed after a normal switch-off
or after lock-out/blocking
min
–1
OEM
1000
1300
1100 1100 1200
37
2FR
32805
Fan afterrun time after operation or blocking
min
OEM
3
3
3
3
3
38
2FU
32806
Fan speed at boiler freeze protection
min
–1
OEM
1500 1500 1500 1500 1500
39
2GA
32807
Waiting time after opening main gas valve
or activation of heating room fan
min
OEM
0
0
0
0
0
40
2GB
32808
External main gas valve/
heating room fan available
OEM
1
1
1
1
1
41
2HA
32809
Afterrun heating pump or shut-off valve
min
HF
5
5
5
5
5
42
2HD
32810
Summer operation (“summer kick”)
sek
OEM
10
10
10
10
10
43
2IA
32811
Ignition (0-> Internal, 1-> In External,
2-> External)
OEM
2
2
2
2
2
44 2KM 32812
Step modulation (0-> off, 1->increasing,
2-> increasing and decreasing)
HF
1
1
1
1
1
45
2LA
32813
Effect of the fault relay
HF
2
2
2
2
2
46
2NA
32814 ADC/4 value at 0 bar
OEM
25
25
25
25
25
47
2NB
32815
ADC/4 value at 6 bar and BIC 960 V.2
OEM
145 145 145 145 145
ADC/4 value at 10 bar and BIC 960 V.3
OEM
225 225 225 225 225
48
2IB
32816
Extended external ignition time
sek
OEM
8
8
8
8
8
49
2CB
32817
Activate/deactivate vacuum and overpressure switch (fan)
(0 -> deactivated, 1 -> activated)
-
OEM
1
1
1
1
1
50 2CC
32818
Reserve
-
OEM
0
0
0
0
0
Adaptations for liquid gas
27 2FF
32795 Fan speed during the first period of pre-venting
min
–1
OEM
4300
5800 5100 6100
6300
28 2FG
32796
Fan speed at start
min
–1
OEM
3500
2500 2500
3000 3000
29 2FH
32797 Maximum fan speed
min
–1
OEM
4300
5800 5100 6100
6300
30
2FI
32798 Minimum fan speed
min
–1
OEM
1400
1500
1400 1300 1400
36
2FO
32804
Fan speed after a normal switch-off
or after lock-out/blocking
min
–1
OEM
1400
1500
1400 1300 1400
47
4 217 213 / 01
PARAMETER LIST - AUTOMATIC FIRING DEVICE BIC 960