6.8
Clean siphon or neutralisation box
1. Set the main system switch to “0”
2.
Remove the front panel (1, Fig. 41)
3.
Unscrew resp. remove (according to execution) si-
phon (3, Fig. 41), siphon bottom part (2) , siphon sup
-
port (2a) or neutralisation box (4, Fig. 42)
4.
Rinse siphon
5.
Check if siphon gaskets (3) are not damaged, replace
if necessary
!
CAUTION
Danger of poisoning!
If the siphon is not filled with water, or be
-
comes blocked or contaminated by impuri-
ties, the flue gas emerging can represent a
potentially fatal hazard.
Before reinserting, fill the siphon with water.
1
2
3
Mount hose for
wet cleaning
Design with condensate discharge
2a
Fig. 41
Design with neutralisation box (if fitted)
1. Set the main system switch to “0”
2.
Remove the front panel (1, Fig. 42)
3. Clean the neutralisation box (4 - if fitted) accourding
1
4
Mount hose for
wet cleaning
Fig. 42
44
4 217 213 / 01
MAINTENANCE