5.6 Heat output
t
F
t
room
Type
Q
H
max
t
S
P
WP
P
E
Δp
W
m
W
°C
°C
TP-
kW
m
°C
kW
kW
kPa
l/h
-15
16
6–K
22.0
15.8
28.9
7.77
–
–
–
6AK
32.1
13.5
33.9
8.45
–
0.0
295.0
6SK
33.9
13.2
34.8
8.58
12.1
–
–
9–K
22.0
19.6
25.3
7.77
–
–
–
9–M
44.0
14.9
32.5
15.54
–
–
–
9AK
38.9
15.7
30.8
8.58
–
0.0
490.0
9RK
35.9
16.2
29.8
8.45
14.0
–
–
9SK
40.0
15.5
31.2
8.58
18.2
–
–
20
6–K
21.9
15.9
32.8
8.31
–
–
–
6AK
–
–
–
–
–
–
–
6SK
25.8
14.9
34.8
8.58
4.0
–
–
9–K
21.9
19.8
29.2
8.31
–
–
–
9–M
43.8
15.0
36.5
16.62
–
–
–
9AK
–
–
–
–
–
–
–
9RK
27.9
18.0
31.2
8.58
6.1
–
–
9SK
27.9
18.0
31.2
8.58
6.1
–
–
Legend:
t
F
= Fresh air temperature
t
room
= Room air temperature
Q
= Heat output
H
max
= Maximum mounting height
t
S
= Supply air temperature
P
HP
= Power consumption of the condensing unit(s)
P
E
= Power consumption of the electric heating coil
Δp
W
= Water pressure drop
m
W
= Water quantity
Reference:
■
At room air temperature 16 °C: extract air temperature 18 °C
■
At room air temperature 20 °C: extract air temperature 22 °C
Supplementary heater with hot water: Flow / Return 55 °C / 25 °C
Table 14: TopVent
®
TP heat output
5.7 Cooling capacity
t
F
t
room
RH
room
Type
Q
sen
Q
tot
t
S
m
C
P
WP
°C
%
%
TP-
kW
kW
°C
kg/h
kW
32
26
50
6…K
20.1
28.4
18.1
12.2
6.90
9…K
19.8
28.4
21.5
12.6
6.90
9–M
39.8
55.4
14.8
22.9
13.47
70
6…K
15.0
29.2
20.6
20.8
6.94
9…K
14.8
29.2
23.2
21.1
6.94
9–M
30.7
54.6
17.9
40.7
13.89
Legend:
t
F
= Fresh air temperature
t
room
= Room air temperature
RH
room
= Relative humidity of the room air
Q
sen
= Sensible cooling capacity
Q
tot
= Total cooling capacity
t
S
= Supply air temperature
m
C
= Condensate quantity
P
HP
= Power consumption of the condensing unit(s)
Reference:
■
At room air temperature 22 °C: extract air temperature 24 °C
■
At room air temperature 26 °C: extract air temperature 28 °C
Table 15: TopVent
®
TP cooling capacity
16
TopVent
®
TP
Technical data
4 218 024-en-04