TECHNICAL INFORMATION
3.2
Technical data
Type
(110)
(130)
(160)
• Nominal output 80/60 °C
105
124
152
• Nominal output 40/30 °C
110
130
160
• Range of output 80/60 °C
kW
78 - 105.0
99 - 124.0
114 -152.0
• Range of output 40/30 °C
kW
83 - 110.0
104 - 130.0
119 -160.0
• Heat input
kW
80 - 105.8
100 - 125.2
115 - 154.0
• Dimensions
Space requirements
• Boiler working temperature max.
°C
90
90
90
• Boiler working temperature min.
°C
no min. limit
•
Return flow temperature min.
°C
no min. limit
• Flue gas temperature min. at the boiler
°C
no min. limit
• Safety temperature limiter setting (water side)
°C
110
110
110
• Working / test pressure
bar
5.0 / 7.5
5.0 / 7.5
5.0 / 7.5
•
Boiler efficiency at 80/60 °C in full-load operation
(net calorific value NCV / gross calorific value GCV) %
99.1 / 93.5
99.0 / 93.4
98.7 / 93.1
•
Boiler efficiency at 40/30 °C in full-load operation
(net calorific value NCV / gross calorific value GCV) %
104.1 / 98.2
104.1 / 98.2
103.9 / 98.0
•
Boiler efficiency at 30 % partial load (EN 303)
(net calorific value NCV / gross calorific value GCV) %
105.0 / 99.1
104.8 / 98.9
104.5 / 98.6
•
Stand-by deficiency qB at 70 °C
Watt
500
500
500
•
Combustion gas resistance, 12.5 % CO
2
, 500 m above sea,
level (tol/- 20 %)
mbar
0.24
0.34
0.45
• Flow resistance boiler
1
z value
0.1
0.1
0.1
• Water resistance at 10 K
mbar
8.9
12.4
18.8
• Water resistance at 20 K
mbar
2.2
3.1
4.7
•
Water flow volume at 10 K
m
3
/h
9.4
11.1
13.7
•
Water flow volume at 20 K
m
3
/h
4.7
5.6
6.9
• Boiler water capacity
litres
340
340
340
• Boiler gas volume
m
3
0.247
0.247
0.247
• Insulation thickness boiler body
mm
80
80
80
• Weight (incl. casing, burner)
kg
420
420
420
• Weight of transport
kg
370
370
370
• Electrical power consumption (during operation) min./max.
Watt
140/360
152/550
167/550
• Standby
Watt
6
6
6
• Acoustic power level incl. sound absorber hood
Ambient air dependent
- Heating noise (EN 15036 part 1)
dB(A)
65
67
67
Ambient air dependent
- Exhaust noise in the pipe (EN 15036 part 2)
2)
dB(A)
86
89
92
- Exhaust noise is radiated from the mouth
(DIN 45635 part 47)
dB(A)
75
76
78
• Condensate rate (heating oil EL) at 40/30 °C
l/h
7.8
8.7
10.8
• pH-value of the condensate
approx.
3.2
3.2
3.2
• Construction type
B23
B23
B23
• Flue gas system
Temperature class
T120
T120
T120
Flue gas mass flow at nominal output 12.5 % CO
2
heating oil EL
kg/h
163.6
193.0
252.0
Flue gas temperature at nominal output 80/60 °C
°C
68
70
75
Maximum supply pressure for supply air and flue gas line
Pa
80
80
80
Maximum draught/underpressure at flue gas outlet
Pa
-20
-20
-20
• Combustion chamber dimensions Ø inside x length
mm
Ø524 x 800
Ø524 x 800
Ø524 x 800
• Combustion chamber volume
m
3
0.172
0.172
0.172
1)
Flow resistance boiler in mbar = Volume flow (m
3
/h)
2
x z factor
2)
Data without silencer, can be reduced by fitting a silencer