6)
Pump-Out Cycle
– (10 second pump-out) – LEDs 1, 4, 3, and 2 are on.
LED 4 (WV
circuit) is on when S4 dip switch 3 & 4 are set to factory default positions of 3 off and
4 on. With S4 dip switch 3 off & 4 on, CB energizes WV during pump-out. The WV
circuit energizes DV through DVR during pump-out cycles.
CAUTION! Do not adjust.
S4 dip switch 3 & 4 must remain in the factory default position of 3 off and
4 on. Otherwise, DV will not energize during pump-out.
Comp and FMRs remain
energized, WV and HGVs energize, LLVs de-energize. PM stops for 2 seconds, then
DVR and WV energize, energizing PM and DV for 10 seconds. When the pump-out
timer terminates, pump-out is complete. The pump-out frequency control is factory set
for every 10th cycle, and generally no adjustment is required. However, where water
quality is bad and the icemaker needs a pump-out more often, the pump-out frequency
can be adjusted as shown in the table.
Timing of the first pump-out is dependent on S4
dip switch 5 & 6 settings. See the table below.
S4 Dip Switch Setting
Pump-Out
Frequency
1st Pump-Out
No. 5
No. 6
OFF
OFF
Every cycle
After 2nd freeze cycle
ON
OFF
Every 2 cycles
After 3rd freeze cycle
OFF
ON
Every 5 cycles
After 6th freeze cycle
ON
ON
Every 10 cycles
After 11th freeze cycle
Diagnosis:
Confirm CB S4 dip switch 3 & 4 settings are in the factory default positions
(3 off and 4 on). Check that Comp continues. Confirm WV and HGVs energize and LLVs
de-energize. Next, check that DVR, PM, and DV energize. If DVR does not energize
(LED 3 on), check CB #5 pin (DBu wire) on CB K1 ten-pin connector for 115VAC. If no
voltage is present CB is bad and must be replaced. If 115VAC is present and DVR is not
energized, check DVR solenoid for open windings. If DVR is energized and PM is not
energized, check PM circuit (including DVR contacts), PM, and PM capacitor. If water
is not going down the drain, check that DV is energized and open. If not, check that CB
LEDs 4 and 3 are on and WV circuit energizes DV during pump-out. Check for 115VAC
at DV solenoid and make sure DV is clear of debris. If water does not pump out, check
and clean DV and tubing.
7)
Normal Harvest Cycle
–
same as the initial harvest cycle – Return to "IV.A.4) Initial
Harvest Cycle."
8)
Shutdown
Bin Control:
See "IV.C.1. Bin Control Check."
Legend:
BC
–bin control;
CB
–control board;
Comp
–compressor;
DV
–drain valve;
DVR
–drain valve relay;
FMRs
–fan motors-remote;
F/S
–float switch;
HGVs
–hot gas
valves (KMS and SRK);
HM
–headmaster (C.P.R.);
LLVs
–liquid line valves (KMS
and SRK);
PM
–pump motor;
TXV
–thermostatic expansion valve;
WV
–inlet water
valve