9. Scheduled
Maintenance
Warning
The Chillers must not be cleaned by a water jet.
The following Chiller routine maintenance should be performed at the intervals listed.
9.1. Scheduled Maintenance
9.1.1. Weekly
As per brewery instructions, ensure weekly sanitisation of the whole beer system is
carried out, including keg couplers, beer lines, chiller coils, pythons, founts and taps.
9.1.2. Monthly
Disconnect the machine from the power supply.
Remove the condenser filter and rinse in warm soapy water.
Re-install the condenser filter.
Check the tank level. Fill if necessary.
Check operation of pump.
Check for beer leaks.
If Glycol type, inspect and if contaminated replace with 30% Glycol and 70% Water
mix.
Check concentration with a refractometer. (see chart below)
Reconnect the machine to the power supply.
Relative freeze points and refractometer readings for propylene glycol / water mix
-30
-20
-10
0
10
20
30
0%
10%
20%
30%
40%
glycol / water mix