8.2.2 Other
Parameters
Setting “F” (frequent) Parameters
Push and hold the “PRG” key for more than 5 seconds.
Select the required parameter to change using the “UP or “DOWN arrow keys then
press the “SET” key to display its value.
Press the “UP” or “DOWN” key to change its value.
Press the “SET” key to store the new value and move to the next parameter.
To exit from programming mode press the “PRG” key for 5 seconds or wait 60 seconds
without pressing any keys for the unit to time out.
8.2.3 Alarm
Signals
When an alarm is activated, the display shows the corresponding message that flashes
alternating with the temperature.
Message Cause
Reset
“E0”
Glycol Probe Failure
Automatic
“E1”
Refrigeration Line Probe Failure
Automatic
“LO”
Low Temperature Alarm
Automatic
“HI”
High Temperature Alarm
Automatic
“AF” Antifreeze
Alarm
Manual
Antifreeze alarm can be reset by holding “UP” and
“DOWN” keys for 5 seconds.