65
Min. 4-3/4"
Liquid Bypass
Flow
10) Secure the insulation using the Plastic Cable Ties.
11) Connect the Thermistor leads through the bushing of the Control Box to the K3
Connector on the Controller Board.
Note: Do not cut the leads of the Thermistor while installing it.
12) Replace the Control Box Cover and the panels in their correct positions.
13) Turn on the power supply.
12. REMOVAL AND REPLACEMENT OF FAN MOTOR
Note: When replacing a Fan Motor with defective winding, it is recommended
that a new capacitor be installed.
1) Turn off the power supply.
2) Remove the panels.
3) Remove the Junction Box Cover from the remote condenser unit (Remote Air-cooled
model).
4) Remove the closed end connectors from the Fan Motor leads.
5) Remove the Fan Motor Bracket and Fan Motor.
6) Install the new Fan Motor, and replace the removed parts in the reverse order of
which they were removed.
7) Replace the panels in their correct positions.
8) Replace the Junction Box Cover in its correct position (Remote Air-cooled model).
9) Turn on the power supply.
Fig. 3
Содержание KM-900MAH
Страница 1: ...6 59 0 18 668 7 2 2 5 2 2 3 4 5 2 5HOLDELOLW LV D EHDXWLIXO WKLQJ70 5 9 6 180 5 73105...
Страница 10: ...10 5 CONDENSING UNIT URC 12F...
Страница 12: ...12 II GENERAL INFORMATION 1 CONSTRUCTION a KM 900MAH Models with Thermostat Models with Mechanical Bin Control...
Страница 13: ...13 b KM 900MWH Models with Thermostat Models with Mechanical Bin Control...
Страница 14: ...14 c KM 900MRH Models with Thermostat Models with Mechanical Bin Control...
Страница 15: ...15 d KM 900MRH3 Models with Thermostat Models with Mechanical Bin Control...
Страница 30: ...30 III TECHNICAL INFORMATION 1 WATER CIRCUIT AND REFRIGERANT CIRCUIT a KM 900MAH...
Страница 31: ...31 b KM 900MWH...
Страница 32: ...32 c KM 900MRH and KM 900MRH3...
Страница 41: ...41 3 TIMING CHART...
Страница 42: ...42...