![Hoshizaki KM-900MAH Скачать руководство пользователя страница 19](http://html1.mh-extra.com/html/hoshizaki/km-900mah/km-900mah_service-manual_2164742019.webp)
19
(Control Products HOS-001A Board)
The application switch located between relay X3 & X4 must be set to match the original
board application. Place this switch in the ALP position if there is no white wire supplied
to the K1 connector. If there is a white wire, place the switch in the C position. If this
switch is placed in the wrong position, either the compressor contactor will remain ener-
gized with the control switch OFF, or the unit will not start.
The dip switches should be adjusted per the adjustment chart published in the Tech
Specs book. Number 8 must remain in the OFF position.
Содержание KM-900MAH
Страница 1: ...6 59 0 18 668 7 2 2 5 2 2 3 4 5 2 5HOLDELOLW LV D EHDXWLIXO WKLQJ70 5 9 6 180 5 73105...
Страница 10: ...10 5 CONDENSING UNIT URC 12F...
Страница 12: ...12 II GENERAL INFORMATION 1 CONSTRUCTION a KM 900MAH Models with Thermostat Models with Mechanical Bin Control...
Страница 13: ...13 b KM 900MWH Models with Thermostat Models with Mechanical Bin Control...
Страница 14: ...14 c KM 900MRH Models with Thermostat Models with Mechanical Bin Control...
Страница 15: ...15 d KM 900MRH3 Models with Thermostat Models with Mechanical Bin Control...
Страница 30: ...30 III TECHNICAL INFORMATION 1 WATER CIRCUIT AND REFRIGERANT CIRCUIT a KM 900MAH...
Страница 31: ...31 b KM 900MWH...
Страница 32: ...32 c KM 900MRH and KM 900MRH3...
Страница 41: ...41 3 TIMING CHART...
Страница 42: ...42...