31
from the hose. For the required refrigerant charge, see the nameplate. Hoshizaki
recommends only virgin refrigerant or reclaimed refrigerant which meets AHRI Standard
700 (latest edition) be used.
6) A liquid charge is required when charging an R-134a system. Place the service cylinder
on the scales; if the service cylinder is not equipped with a dip tube, invert the service
cylinder, then place it on the scales. Open the high-side valve on the gauge manifold.
7) Allow the system to charge with liquid until the proper charge weight is met.
8) Close the high-side valve on the gauge manifold, then close the refrigerant access valve (if
applicable). Disconnect the gauge manifold hose.
9) Cap the access valve to prevent a possible leak.
B. Component Service Information
1. Cabinet
Rear Panel
Top Insulation
Top Panel
Top Panel
Bracket
Front Panel
(Lower)
Bracket
Top Cover
Drain Pan
Tab
Slope
Front Frame
Front Frame
Top Panel Bracket
Door (Assy)
[a] Top Panel, Top Insulation, Top Cover
1) Remove the top panel bracket (at both sides of the front) hooking the front of the top
panel.
2) Lift up the front of the top panel, slide it to the rear by 2/5" (10 mm), and lift it off. The
top insulation and top cover (fitted in the top panel) come off together with the top
panel.
3) Replace the removed parts in the reverse order of the removal procedure.