27
4) Press the "RESET" button to return to list. To clear error log history, press and hold the
"SERVICE 1" and "SERVICE 2" buttons simultaneously for 5 sec.
5) Display returns to normal if no buttons are touched for 20 sec.
Error Codes
Error Item
Description
Operation Reset
E1
Freeze error
Freeze backup timer (45 minutes
after water tank assembly starts to close)
counts
up before freeze cycle completes, and
evaporator temperature is 32°F (0°C) or
higher.
Shut down Press "RESET" button
E2
Harvest error
Harvest backup timer (30 minutes after
water tank starts to open) counts up
before harvest cycle completes.
Shut down Press "RESET" button
EE
(E3)
Water tank
assembly opening
error
Water tank assembly has not fully opened
within 60 seconds, and 3 minutes have
passed even with opening failure control.
Halt
Press "RESET" button
Unit resumes operation after 60 minutes
and repeats the above error.
Shut down
EE
(E4)
Water tank
assebmly closing
error
Water tank assembly has not fully closed
within 50 seconds, opened and started to
close again, but failed to close fully within
50 seconds.
Halt
Press "RESET" button
Unit resumes operation after 60 minutes
and repeats the above error.
Shut down
EE
(E5)
High temperature
error
Evaporator temperature stays 140°F
(60°C) or higher for 5 seconds or more.
Shut down Press "RESET" button
EE
(E7)
Fan motor lock
Fan motor is locked for 30 seconds with
control voltage applied.
Shut down Press "RESET" button
EE
(E8)
Pump motor lock
Pump motor is locked for 30 seconds with
control voltage applied.
Continue
Press "RESET" button
Unit detects the above error 3 times.
Shut down
EE
(EA)
Data error
Model setting data memory IC is
defective.
Shut down Replace control board
EE
(EC)
Evaporator (cube
control) thermistor
error
Evaporator (cube control) thermistor
circuit is open or shorted for 2 seconds.
Shut down Replace thermistor