VI. REMOVAL AND REPLACEMENT OF COMPONENTS
1. SERVICE FOR REFRIGERANT LINES
[a] REFRIGERANT RECOVERY
The icemaker unit is provided with two Refrigerant Access Valves - one on the low-side
and one on the high-side line. Using proper refrigerant practices recover the refrigerant
from the Access Valves and store it in an approved container. Do not discharge the refrig-
erant into the atmosphere.
[b] EVACUATION AND RECHARGE [R-404A]
1) Attach Charging Hoses, a Service Manifold and a Vacuum Pump to the system. Be
sure to connect Charging Hoses to both High-side and Low-side Access Valves.
IMPORTANT
The vacuum level and vacuum pump may be the same as those for current
refrigerants. However, the rubber hose and gauge manifold to be used for
evacuation and refrigerant charge should be exclusively for POE oils.
2) Turn on the Vacuum Pump. Never allow the oil in the Vacuum Pump to flow backward.
3) Allow the Vacuum Pump to pull down to a 29.9" Hg vacuum. Evacuating period de-
pends on pump capacity.
IMPORTANT
Ensure all components, fasteners and thumbscrews are securely in place
after the equipment is serviced.
IMPORTANT
1. The Polyolester (POE) oils used in R-404A units can absorb moisture
quickly. Therefore it is important to prevent moisture from entering the
system when replacing or servicing parts.
2. Always install a new filter drier every time the sealed refrigeration sys-
tem is opened.
3. Do not leave the system open for longer than 15 minutes when replac-
ing or servicing parts.
Содержание F-800MAF
Страница 9: ...9 2 CONDENSER UNIT URC 6F ...
Страница 15: ...15 III TECHNICAL INFORMATION 1 WATER CIRCUIT AND REFRIGERATION CIRCUIT F 800MAF C ...
Страница 16: ...16 F 800MWF C ...
Страница 17: ...17 2 WIRING DIAGRAMS F 800MAF C F 800MWF C ...
Страница 19: ...19 b When Reservoir has been filled Gear Motor starts immediately ...
Страница 20: ...20 c Compressor starts about 60 sec after Gear Motor starts ...
Страница 21: ...21 d Bin Control operates and about 6 sec later Compressor and Gear Motor stop simultaneously ...
Страница 22: ...22 e Low Water Except Water cooled Model ...
Страница 24: ...24 g When Flush Switch is moved to FLUSH position Flush Water Valve opens and flushes Reservoir and Evaporator ...
Страница 25: ...25 h When Flush Timer operates for 15 min every 12 hours ...