30
1. CIRCUIT PROTECT
RELAY
2. WATER LEVEL
3. FLOAT
SWITCH
UPPER
LOWER
4. WATER CONTROL
RELAY
5. CONTROL WATER
VALVE
6. FLUSH TIMER
7. FLUSH SWITCH
8. FLUSH WATER
VALVE
9. BIN CONTROL
10. GEAR MOTOR
RELAY
11. GEAR MOTOR
12. FAN MOTOR
14. PRESSURE
SWITCH
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
1 - 2
2 - 3
FLUSH
ICE
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
UPPER
LOWER
BOTTOM
FLUSH SWITCH
PRESSURE SWITCH
FLUSH
ICE
OFF
ON
150 sec
1 sec
90 sec
60 sec
13. COMPRESSOR
1 sec
1 sec
60 sec
Содержание F-800MAF
Страница 9: ...9 2 CONDENSER UNIT URC 6F ...
Страница 15: ...15 III TECHNICAL INFORMATION 1 WATER CIRCUIT AND REFRIGERATION CIRCUIT F 800MAF C ...
Страница 16: ...16 F 800MWF C ...
Страница 17: ...17 2 WIRING DIAGRAMS F 800MAF C F 800MWF C ...
Страница 19: ...19 b When Reservoir has been filled Gear Motor starts immediately ...
Страница 20: ...20 c Compressor starts about 60 sec after Gear Motor starts ...
Страница 21: ...21 d Bin Control operates and about 6 sec later Compressor and Gear Motor stop simultaneously ...
Страница 22: ...22 e Low Water Except Water cooled Model ...
Страница 24: ...24 g When Flush Switch is moved to FLUSH position Flush Water Valve opens and flushes Reservoir and Evaporator ...
Страница 25: ...25 h When Flush Timer operates for 15 min every 12 hours ...