IV. ADJUSTMENT OF COMPONENTS
1. ADJUSTMENT OF WATER REGULATING VALVE - WATER-COOLED
MODEL ONLY
The Water Regulating Valve or also called “WATER REGULATOR” is factory-adjusted. No
adjustment is required under normal use. Adjust the Water Regulator , if necessary, using
the following procedures.
1) Attach a pressure gauge to the high-side line of the system. Or prepare a thermometer
to check the condenser drain temperature.
2) Rotate the Adjustment Screw by using a flat blade screwdriver, so that the pressure
gauge shows 260 PSIG (R-404A models/-F type), or the thermometer reads 100 -104°F,
in 5 minutes after the icemaking process starts. When the pressure exceeds 260 PSIG,
or the condenser drain temperature exceeds 104°F, rotate the Adjustment Screw
counterclockwise.
3) Check that the pressure or the condenser drain temperature holds a stable setting.
Adjustment Screw
Adjustment Screw
Bottom View
CW - Higher
CCW - Lower
CW
CCW
Содержание F-800MAF
Страница 9: ...9 2 CONDENSER UNIT URC 6F ...
Страница 15: ...15 III TECHNICAL INFORMATION 1 WATER CIRCUIT AND REFRIGERATION CIRCUIT F 800MAF C ...
Страница 16: ...16 F 800MWF C ...
Страница 17: ...17 2 WIRING DIAGRAMS F 800MAF C F 800MWF C ...
Страница 19: ...19 b When Reservoir has been filled Gear Motor starts immediately ...
Страница 20: ...20 c Compressor starts about 60 sec after Gear Motor starts ...
Страница 21: ...21 d Bin Control operates and about 6 sec later Compressor and Gear Motor stop simultaneously ...
Страница 22: ...22 e Low Water Except Water cooled Model ...
Страница 24: ...24 g When Flush Switch is moved to FLUSH position Flush Water Valve opens and flushes Reservoir and Evaporator ...
Страница 25: ...25 h When Flush Timer operates for 15 min every 12 hours ...