HTTP/HTTPS
W
EB
GUI
–
W
EB
B
ROWSER
C
ONFIGURATION
I
NTERFACE
8030HEPTA/GPS GPS - NTP Time Server with 2x 10/100/1000 MBit LAN Interface - V04.00
48 / 178
hopf
Elektronik GmbH
Nottebohmstr. 41
• D-58511 Lüdenscheid • Tel.: +49 (0)2351 9386-86 • Fax: +49 (0)2351 9386-93 • Internet: http://www.hopf.com • E-Mail: [email protected]
If the data should only be tested it is sufficient to accept the changes with
Apply
.
Changing Network Parameters
Modifications of the network parameters (e.g. IP address) are immediately
effective clicking on
Apply
to confirm.
However, the modifications are not permanently saved yet. This requires
to access the WebGUI with the new network parameters again and to
save the data with
Save
permanently.
For adopting changes and entering values only the respective buttons in
the WebGUI can be used.
8.2.3.2 Changing of Data in 8024GPS (WebGUI: GPS Sync Source)
The modified data in the GPS SYNC SOURCE tab are directly transferred to the Module
8024GPS by pushing the button 1 and stored failsafe in Module 8024GPS. Tabs with settings
and values modified in this manner can also be recognized by the modified display of the
Apply
button. The buttons 2 and 3 in GPS SYNC SOURCE tab are disabled and are not
required.
The new reading of the modified data from Module 8030HEPTA for the
WebGUI indication can take up to 30 seconds after data transfer to Mod-
ule 8024GPS.
However, this has no effect on the function of the appropriate set-
ting/value.