C
OMMISSIONING
8030HEPTA/GPS GPS - NTP Time Server with 2x 10/100/1000 MBit LAN Interface - V04.00
29 / 178
hopf
Elektronik GmbH
Nottebohmstr. 41
• D-58511 Lüdenscheid • Tel.: +49 (0)2351 9386-86 • Fax: +49 (0)2351 9386-93 • Internet: http://www.hopf.com • E-Mail: [email protected]
6
Commissioning
This chapter describes commissioning of the Time Server 8030HEPTA/GPS.
6.1
General Procedure
Overview of the general commissioning procedure:
•
Finish the installation process completely
•
Switch on the device
•
Wait until the booting phase is finished (see
Chapter 4.1 Boot Phase
•
Using the SEARCH Function of the separate
hmc
Software (Network Configuration
Assistant) in order to access the Time Server 8030HEPTA/GPS and set the basis LAN
parameters (e.g. DHCP). Afterwards connect to the WebGUI of the Time Server
8030HEPTA/GPS via Web browser
OR
Connect directly with the factory default IPv4-address (ETH0: 192.168.0.1 or ETH1 in
DHCP) to the WebGUI of the Time Server 8030HEPTA/GPS via Web browser
•
Log in as
"master"
•
Change default passwords for
"master"
and
"device"
In the
DEVICE tab
•
Set all required LAN parameters (e.g. entry of DNS server) in
NETWORK tab
if nec-
essary
•
Check current settings in
NTP tab
and modify according to individual needs as nec-
essary
•
Parameterize following values of the Sync Source (here Module 8024GPS) in
GPS
SYNC SOURCE
tab:
o
Set current UTC time
o
Set the local difference time to UTC
o
Set or deactivate the changeover times for summer/winter time
o
Check values for reception mode, SyncON/SyncOFF Timer and status OC
Trigger a
Module Reset
after the above mentioned entries
During first commissioning it is mandatory required to configure the differ-
ence time to UTC and the changeover times for summer/winter time re-
spectively to deactivate them one time. Otherwise synchronization via GPS
will not be possible and a "Sync Source Error" is indicated.
•
Check for
Module Error
in register
GPS SYNC SOURCE
•
Parameterize optional functions e.g. SNMP or SINEC H1 time datagram