6.3.3.5 External Alarm Messages (optional)
The Management Board 7052RC optionally provides eight (8) TTL compatible monitoring in-
puts within the system that are available for sending alarm messages released by the change
of the input signal.
Each monitoring input is separately configured:
Active:
Activation / Deactivation of the monitoring input for release of alarm messages.
Label:
Naming of the monitoring input for a better identification of the alarm message, maximal 65
ASCII characters possible.
Alarm Level:
The alarm level indicates the priority level of the alarm message to be sent.
Alarm Trigger:
The Alarm Trigger indicates the change of signal input causing sending of the alarm message.
Alarm Trigger
Change of Signal
Display
TTL Input Signal
Rising Edge
Rising
Off
On
5V
0V
Falling Edge
Falling
On
Off
0V
5V
Both Edges
Rising and Falling
Off
On
On
Off
5V
0V
0V
5V