EXCEL 10 W7761A INPUT/OUTPUT DEVICE
35
74-2699
Table 8. Excel 10 W7761A Device Ordering Information (Continued).
Part Number
Product Description
Comments
Accessories (Continued):
ML6474A1008
Direct Coupled Actuator, 132 lb-in. torque, Series 60
—
ML6185A1000
Direct Coupled Actuator, 50 lb-in. spring return
Series 60
EL7680A1008
Wall Mounted Wide View Infrared Occupancy Sensor
—
EL7628A1007
Ceiling Mounted Infrared Occupancy Sensor
—
EL7611A1003,
EL7612A1001
Ultrasonic Occupancy Sensors
—
EL7630A1003,
EL7621A1002,
EL7621A1010
Power Supply/Control Units for Occupancy sensors
—
C7400A1004
Solid State Enthalpy Sensor (4 to 20 mA)
For outdoor and return air enthalpy
C7600B1000
Solid State Humidity Sensor (2 to 10 V)
For outdoor and return air humidity
C7600C1008
Solid State Humidity Sensor (4 to 20 mA)
For outdoor and return air humidity
C7600C1018
Solid State Humidity Sensor (2 to 10 V)
For outdoor and return air humidity
MMC325-010,
MMC325-020
Pneumatic Retrofit Transducers.
Select pressure range: (010) 0 to 10 psi (68.97 kPa)
or (020) 0 to 20 psi (137.93 kPa).
Use to control Pneumatic reheat valves
MMCA530
DIN rail adapter for MMC325 Transducers
—
MMCA540
Metal enclosure for MMC325 Transducers
—
ML7984B3000
Valve Actuator Pulse Width Modulation (PWM)
Use with V5011 or V5013 F and G Valves
ML6161B1000
Damper Actuator Series 60
—
M6410A
Valve Actuator Series 60
Use with V5812/V5813 Valves
ML684A1025
Versadrive Valve Actuator with linkage, Series 60
Use with V5011 and V5013 Valves
ML6464A1009
Direct Coupled Actuator, 66 lb-in., Series 60
—
ML6474A1008
Direct Coupled Actuator, 132 lb-in. torque, Series 60
—
ML6185A1000
Direct Coupled Actuator, 50 lb-in. spring return
Series 60
V5812A
Two-way terminal unit water valve; 0.19, 0.29, 0.47,
0.74, 1.2, and 1.9 Cv 1/2 in. npt (13 mm) or
2.9 and 4.9 Cv 3/4 in. npt (19 mm)
Use with M6410 Valve Actuator. Close-off
rating for 0.19 to 1.9 Cv is 65 psi; for 2.9
and 4.9, Cv is 45 psi. (Coefficient of
volume or capacity index Cv = gallons per
minute divided by the square root of the
pressure drop across the valve.)
V5813A
Three-way mixing terminal unit hot water valve; 0.19,
0.29, 0.47, 0.74, 1.2, and 1.9 Cv 1/2 in. npt (13 mm)
or 2.9 and 4.9 Cv 3/4 in. npt (19 mm)
Use with M6410 Valve Actuator. Close-off
rating 0.19 to 0.74 Cv is 55 psi; 1.2, and
1.9 Cv is 22 psi; 2.9 and 4.9 Cv is 26 psi.
R8242A
Contactor, 24 Vac coil, DPDT
—
AT72D, AT88A, AK3310, etc. Transformers
—
EN 50 022
DIN rail 35 mm by 7.5 mm (1-3/8 in. by 5/16 in.)
Obtain locally: A controller requires 5 in.
—
Augat Inc. part number 2TK2D DIN rail (adapter)
Purchase from Augat Inc. two DIN rail
adapters for each controller
—
Serial Interface Cable, male DB-9 to female DB-9 or
female DB-25.
Obtain locally from any computer
hardware vendor.
Cabling
Honeywell AK3791 (one
twisted pair) AK3792 (two
twisted pairs)
E-Bus (plenum): 22 AWG (0.34 mm
2
) twisted pair
solid conductor, nonshielded or Echelon
approved
cable.
Level IV 140°F (60°C) rating
Honeywell AK3781 (one
twisted pair) AK3782 (two
twisted pairs)
E-Bus (nonplenum): 22 AWG (0.34 mm
2
) twisted pair
solid conductor, nonshielded or Echelon
approved
cable.
Level IV 140°F (60°C) rating
Honeywell AK3725
Inputs: 18 AWG (1.0 mm
2
) five wire cable bundle
Standard thermostat wire
(continued)