EXCEL 10 W7761A INPUT/OUTPUT DEVICE
67
74-2699
Table C4. Configuration Parameters (Left Continued).
Engineering Units:
English (Metric) or
Digital
State
or
Value
of
User Address
NvName
Field Name
States plus Range
State
Default
DO5FlSpeed
nciFloatConfig
DO4
seconds
0 to 900
90
DO6FlSpeed
nciFloatConfig
DO5
seconds
0 to 900
90
DO7FlSpeed
nciFloatConfig
DO6
seconds
0 to 900
90
DO8FlSpeed
nciFloatConfig
DO7
seconds
0 to 900
90
DO1PWMPeriod
nciPWMConfig1
DO0.si_period_pwm
seconds
0.0 to 3000
25.6
DO1PWMZero
nciPWMConfig1
DO0.si_pnct_time
seconds 0.0 to 3000
0.1
DO1PWMFull
nciPWMConfig1
DO0.si_delta_time
seconds 0.0 to 3000
25.5
DO2PWMPeriod
nciPWMConfig1
DO1.si_period_pwm
seconds 0.0 to 3000
25.6
DO2PWMZero
nciPWMConfig1
DO1.si_pnct_time
seconds 0.0 to 3000
0.1
DO2PWMFull
nciPWMConfig1
DO1.si_delta_time
seconds 0.0 to 3000
25.5
DO3PWMPeriod
nciPWMConfig1
DO2.si_period_pwm
seconds 0.0 to 3000
25.6
DO3PWMZero
nciPWMConfig1
DO2.si_pnct_time
seconds 0.0 to 3000
0.1
DO3PWMFull
nciPWMConfig1
DO2.si_delta_time
seconds 0.0 to 3000
25.5
DO4PWMPeriod
nciPWMConfig1
DO3.si_period_pwm
seconds 0.0 to 3000
25.6
DO4PWMZero
nciPWMConfig1
DO3.si_pnct_time
seconds 0.0 to 3000
0.1
DO4PWMFull
nciPWMConfig1
DO3.si_delta_time
seconds 0.0 to 3000
25.5
DO5PWMPeriod
nciPWMConfig2
DO4.si_period_pwm
seconds 0.0 to 3000
25.6
DO5PWMZero
nciPWMConfig2
DO4.si_pnct_time
seconds 0.0 to 3000
0.1
DO5PWMFull
nciPWMConfig2
DO4.si_delta_time
seconds 0.0 to 3000
25.5
(continued)