EXCEL 10 W7761A INPUT/OUTPUT DEVICE
51
74-2699
Table C1. Input/Output Points (Left Continued).
Engineering Units:
English (Metric) or
Digital
State
or
Value
of
User Address
NvName
Field Name
States plus Range
State
Default
DO2Type
ncirioIoSelect
DigitalOut1
Refer to the Eng. Units/States
column for DO1Type for selections
available.
Unused_DigOutput
DO3Type
ncirioIoSelect
DigitalOut2
Refer to the Eng. Units/States
column for DO1Type for selections
available.
Unused_DigOutput
DO4Type
ncirioIoSelect
DigitalOut3
Refer to the Eng. Units/States
column for DO1Type for selections
available.
Unused_DigOutput
DO5Type
ncirioIoSelect
DigitalOut4
Refer to the Eng. Units/States
column for DO1Type for selections
available.
Unused_DigOutput
DO6Type
ncirioIoSelect
DigitalOut5
Refer to the Eng. Units/States
column for DO1Type for selections
available.
Unused_DigOutput
DO7Type
ncirioIoSelect
DigitalOut6
Refer to the Eng. Units/States
column for DO1Type for selections
available.
Unused_DigOutput
DO8Type
ncirioIoSelect
DigitalOut7
Refer to the Eng. Units/States
column for DO1Type for selections
available.
Unused_DigOutput
FiftySixtyHz
nciIoSelect
FiftySixtyHz
Sixty
Fifty
0
1
Sixty
SrcCO2Level
nvoRemoteCO2
PPM
0 to 65535
0
SrcCurrentAI
nvoRemoteCurrent
milliamps
-20.0 to 200.0
0
SrcDigIn1Sts
nvoRemoteDigIn(0)
DI1Value
0 to 255
0
nvoRemoteDigIn(0)
DI1State
ST_OFF
ST_LOW
ST_MED
ST_HIGH
ST_ON
ST_NUL
0
1
2
3
4
255
ST_NUL