EXCEL 10 W7761A INPUT/OUTPUT DEVICE
45
74-2699
Table C1. Input/Output Points (Left).
Engineering Units:
English (Metric) or
Digital
State
or
Value
of
User Address
NvName
Field Name
States plus Range
State
Default
AI1RType
ncirioIoSelect
ResistiveIn0
DA_Temp_PT3000
OA_Temp_PT3000
RA_Temp_PT3000
Custom_PT3000
DA_Temp_20KNTC
RA_Temp_20KNTC
Space_Temp_T7770
Custom_20KNTC
Unused_Res_AI
0
1
2
3
4
5
6
7
255
Unused_Res_AI
AI2RType
ncirioIoSelect
ResistiveIn1
See AI1RType Eng. Units/States
column for selections
Unused_Res_AI
AI3RType
ncirioIoSelect
ResistiveIn2
See AI1RType Eng. Units/States
column for selections
Unused_Res_AI
AI4RType
ncirioIoSelect
ResistiveIn3
See AI1RType Eng. Units/States
column for selections
Unused_Res_AI
AI5VType
ncirioIoSelect
VoltageIn0
RA_Hum_C7600C
OA_Hum_C7600C
Filter_Diff_Pres
RA_Hum_C7600B
OA_Hum_C7600B
RA_Enthalpy
OA_Enthalpy
Space_CO2
Voltage_Monitor
Unused_Volt_AI
0
1
2
3
4
5
6
7
8
255
Unused_Volt_AI
AI6VType
ncirioIoSelect
VoltageIn1
See AI5VType Eng. Units/States
column for selections
Unused_Volt_AI
(continued)