EXCEL 10 W7761A INPUT/OUTPUT DEVICE
42
74-2699
displayed. Select the project and the Zone manager within that project that is being exported and the
Export button. Exit
CARE and Start E-Vision. Select the E-Vision project to open and the CARE Export Filename created previously. Once
the project is open, select the RIO device that the Digital Output is connected to and go into the Application Selection
screen (offline) by selecting the
Controller, Application Selection menu items. From the Outputs tab of the Application
Selection dialog box, select the first Unused_DigOutput and scroll up until Discrete1 is displayed and select it. Select the
OK button to save the selection.
4. Select the
Controller menu item and then Import from CARE to import the Zone Manager files with the new pseudo
analog point. If this function has already been performed before, the user will be prompted with the message
CARE
Export File has already been imported, do you want to import again?. Select Yes to continue with the Import. When the
import is finished, E-Vision displays the message
CARE Export File has been imported. Select OK to continue.
5. Select the
Network menu item and then Map C-Bus Points. Select RIO1 as the Controller Type from the Map C-Bus
Points dialog box. Under Unmapped CARE, select the name of the RIO device that the Digital Output was added to in
CARE. Under
Unmapped Excel 10, select the name of the RIO device that the actual Digital Output was added to (both
names should be the same). Next, select the
Custom button and the Custom Mapping CARE Points dialog box will be
displayed. Select the
MiscExhFan point under CARE Points and DigOut1Cmd under Excel 10. Select the Map button to
add the
MiscExhFan point to the list of Mapped Points. Click on the Close button to exit the Custom Mapping CARE
Points dialog box. Click on the Close button to exit the Map C-Bus Points dialog box.
6. Re-commission the RIO device that had the custom mapping done.
7. Select the Controller menu item and the Update Zone Manager Files. E-Vision will add the custom mapping information
to the Zone Manager files. When the Update Zone Manager Files function is done, close the E-Vision project and exit out
of E-Vision.
8. Start CARE and open the Zone Manager that was just updated through the Update Zone Manager Files function and
start XI584 by selecting the
Controller, Tools and XI584 menu items. Once XI584 is started, select the Utilities, File
Transfer menu items and select CARE Import. Select the project and the Zone Manager that was just updated and select
Import and click OK on the Select Target Controller dialog box. When the CARE Import is complete, close the CARE
Import dialog box. If this is the initial loading of the Zone Manager, then it will have to be reset and the CPU address set
by the XI581 Emulation function (
Applications, XI581 Emulation menu). Select the Utilities, File Transfer menu items and
select
Download. The Download dialog box will be displayed. Check the All selection and click the Controller button.
When the
Select Controller/Subsystem dialog box is displayed, make sure that the correct CPU address or name is
highlighted and select the
OK button. Click the Download button and Yes to the message Replace updated application
part in controller (CPU address or Controller name). When the download is complete, exit out of the
Download dialog
box. From the
XI584 main menu, select the Data, Access by User Address menu items. Type MiscExhFan in the Search
For User Address and click on the Search button. When the MiscExhFan point displays in the User Addresses list, click
on the point and select the
Attributes button. XI584 will now display the value of the Digital Output connected to the RIO
device. To command the
MiscExhFan to the On mode, put the point in the Manual mode and enter a value of 1.0 or
greater. To command the MiscExhFan to the Off mode, put the point in the Manual mode and enter a value of 0.0. This
point can now be used in the Zone Manager control strategy or switching logic and Time Programs. This point can be
used in other Excel 5000 controllers (C-Bus) by assigning a global analog point in the destination controller with the user
address name of MiscExhFan. Refer to the CARE User’s Manual form, 74-5587 for information on creating global points
in Excel 5000 controllers.
Table A-3. Supported Digital Output Types.
E-Vision Enumerated Name in the Output
Application Selection Tab
RIO Network Variable that contains the
Hardware Output Value
Float1_Open through Float8_Open (Series 60 -
requires two outputs assigned. Float1_Open
must be assigned before Float1_Close)
DigOut1Cmd through DigOut8Cmd
Float1_Close through Float8_Close (Series 60
- requires two outputs assigned. Float1_Open
must be assigned before Float1_Close)
DigOut1Cmd through DigOut8Cmd
Discrete1 through Discrete8 (Maintained On/Off
outputs)
DigOut1Cmd through DigOut8Cmd
Modulate1 through Modulate8 (PWM outputs)
DigOut1Cmd through DigOut8Cmd
Appendix B. Sequences of Operation.
Common Operations
The Excel 10 W7761A Device contains inputs and outputs, but no control software. All control that would be associated with
the inputs and outputs in the W7761A would be accomplished though the Excel Zone Manager and would not be suitable for
VAV control, temperature control, or any control function that would require less than a 30 second update rate. The analog and
digital sensors could be shared or bound to other Excel 10 controllers on the E-Bus or Excel 5000 controllers on the C-Bus
through the Excel 10 Zone Manager. This would allow the other Excel 10 controllers to use their physical inputs for monitoring
other elements such as return humidity, IAQ, etc. to achieve better control.
Room Temperature Sensor (RmTemp)